SECONDARY MENU ITEM DESCRIPTIONS
INDOOR-OUTDOOR RESET MODE
FUNC
REFT
RR
OSAT
Oat
LLT
This displays the mode of the
temperature controller. Common
modes are Oart, indoor\outdoor
reset, Cont, constant setpoint, and
FDFO for a water heater.
This is the building reference
temperature. It is the desired
temperature that the inside of the
building is to maintained.
Reset Ratio is a number that the
header temperature will increase, per
degree, with each degree change in
outside air temperature
This menu item turns the outside air
enable\disable feature on or off.
When ON, an outside air temperature
can be chosen to enable or disable
the unit.
Oat displays the outside air
temperature that the unit is enabled.
This parameter is displayed only
when OSAT is on.
This is Low Limit Temperature alarm.
This feature shuts down the unit and
places the temperature controller into
alarm if the outlet water temperature
goes below this setting. Outlet water
temperature must be higher than the
low limit alarm setting for the unit to
restart.