CONTROL PANEL OPERATING PROCEDURES
8/1/99
3-4
In manual mode, the controller no longer
automatically controls the firing rate of the unit. It
is up to the operator to control the outlet
temperature and firing rate. Manual mode is
commonly used for service and troubleshooting
the unit. All safety controls remain functional
whether the controller is in automatic or manual
mode.
To place the controller in automatic mode press
the MENU button until (Auto) is displayed in the
lower LED.
Now press the
or
arrow keys until ON is
displayed in the upper LED (see fig 3.6). Press
the enter button to accept the change. The MAN
LED should not be lit.
3.6
Auto/ Manual Display with Auto On
To place the temperature controller in manual
mode, press the
or
arrow keys until OFF is
displayed in the upper LED. (See Fig 3.7). Press
the enter button to accept the change. The MAN
LED should now be lit.
3.7
Auto/Manual Display with Manual On
3.4 THE SECONDARY MENU
The secondary menu is used to set temperature
control parameters. It is necessary to access
this menu when setting PID values or changing
the unit mode of operation.
To access the secondary menu, press the
arrow key and ENTER simultaneously. To scroll
through the menu press the MENU button.
The secondary menu allows access to the
following temperature control features:
Func
Mode of 0peration
REFT
Building reference
temperature
RR
Reset Ratio
OSAT
Outside air sensor
feature
Oat
Maximum outside air
temperature that unit
is enabled to run
LLT
Low temperature
alarm setpoint
HLt
High temperature
alarm setpoint
Pb1
Proportional Band
Int
Integral Rate
Drt
Derivative Time
Addr
Controller address
for external
communication
Lore
Local/ remote status
of the control
For a complete explanation of the secondary
menu parameters see Appendix A of this
manual.
3.5 STATUS ANNUNCIATOR
The status annunciator consists of the
annunciator circuit board, the front panel LCD
display, and four function switches. Figure 3.8
show the location of the LCD and four function
switches. The annunciator circuit board is the
interface between the LCD display and the
combustion safeguard system. It monitors the
unit during every phase of operation and
displays start sequence and fault messages.
The function switches are used to reset the
annunciator and gain access to the
annunciator’s three function menus.
Summary of Contents for Benchmark G-00-711
Page 62: ...APPENDIX C ix Temperature Sensor Resistance Chart Balco ...
Page 69: ...APPENDIX F xvi ...
Page 70: ...APPENDIX F xvii ...
Page 71: ...APPENDIX F xviii ...
Page 72: ...APPENDIX F xix ...
Page 73: ...APPENDIX F xx ...
Page 74: ...APPENDIX G xviii ...
Page 75: ...APPENDIX G xix ...
Page 76: ...APPENDIX H xxi ...