INITIAL START-UP
4-2
Figure 4.1
1/8” Gas Plug Location
4.2.3 PREPARING THE FLUE VENT
PROBE HOLE
1. If the unit has been installed using the
recommended AL29-4C vent, there will be a
3/8” hole, in the center of the starter section
(Part #123679). The outer vent section, that
covers the vent section connections must be
loosened and slid down to uncover the hole
(see Fig. 4.2)
2. Adjust the stop on the combustion analyzer
probe, if so equipped, so that it extends
approximately midway into the flue gas flow.
Do not insert the probe at this time.
Figure 4.2
Analyzer Probe Hole Location
Figure 4.3
Differential Regulator Adjustment Tool
Installation
4.2.4 INSTALLING THE DIFFERENTIAL
REGULATOR ADJUSTMENT TOOL
1. Remove the cap from the differential
pressure regulator (see Fig. 4.3).
2. Place the gasket from the regulator cap onto
the regulator adjustment tool.
3. Prior to installing the tool on the regulator,
pull up the screwdriver blade of the tool.
Then thread the tool into the regulator.
4. Engage the tool’s screwdriver blade into the
regulator’s adjustment screw slot.
4.3 COMBUSTION CALIBRATION
The Benchmark ships combustion calibrated
from the factory. Recalibration as part of a start-
up is necessary due to altitude, gas BTU
content, gas supply piping and supply
regulators. Factory test data sheets are shipped
with each unit as a reference.
It is important to perform the following procedure
as outlined. Following this procedure as outlined
will to keep readjustment to a minimum and
provide for optimum performance.
1. Open the water supply and return valves to
the unit and ensure that the system pumps
are running.
2. Open the gas supply valve(s) to the unit.
3. Using the 16” manometer ensure that there
is adequate supply gas pressure. If using a
non-lock up regulator, static pressure should
be between 9" to 14" WC, but no higher than
14" WC. If using a lock-up style regulator
adjust the static supply gas pressure for
approximately 9" WC.
EXHAUST MANIFOLD
COMBUSTION ANALYZER PROBE
LOCATION
STARTER SECTION
REGULATOR CAP
REGULATOR
ADJUSTMENT
TOOL (P.N. 123643)
CAP GASKET
DIFFERENTIAL PRESSURE
REGULATOR
Summary of Contents for Benchmark G-00-711
Page 62: ...APPENDIX C ix Temperature Sensor Resistance Chart Balco ...
Page 69: ...APPENDIX F xvi ...
Page 70: ...APPENDIX F xvii ...
Page 71: ...APPENDIX F xviii ...
Page 72: ...APPENDIX F xix ...
Page 73: ...APPENDIX F xx ...
Page 74: ...APPENDIX G xviii ...
Page 75: ...APPENDIX G xix ...
Page 76: ...APPENDIX H xxi ...