BMK 750-3k Platinum Boiler OPERATION, SERVICE, and MAINTENANCE GUIDE
APPENDIX A: BOILER MENU DESCRIPTIONS
Page
92
of
178
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0116_0A
03/15/2017
Ph.: 800-526-0288
GF-201
TABLE A-3: CONFIGURATION MENU ITEM DESCRIPTIONS
MENU OPTIONS
DESCRIPTION
25
26
Deadband High
Deadband Low
Deadband High and Deadband Low settings create an “Outlet
Temperature” Zone in which no Valve Position corrections will
be attempted.
The Deadband ZONE is defined as operating with an Outlet
Temperature between Active Se Deadband High and
Active Setpoint – Deadband Low.
When the Outlet Temperature reaches Active Setpoint and
remains there for a period of 15 seconds, the unit will go into a
DEADBAND MODE at which point no Valve Position
corrections will be attempted while the Outlet Temperature
remains anywhere within the Deadband ZONE. When the unit
is in the DEADBAND MODE, the °F or °C LED will flash on and
off. When the Outlet Temperature drifts out of the Deadband
ZONE, the DEADBAND MODE will be terminated and the PID
LOOP will again attempt Valve Position corrections.
Setting range is 0°F (0°C) to 25°F (13.75°C). Default is 5°F
(2.75°C) for both Deadband High and Deadband Low).
27
IGST Version
Displays the version of the IGST Board installed.
28
IGN Time Setting
Displays the MAX Ignition time of 4 Seconds or 7 Seconds as
set in the Safety String Harness.
29
Slow Shutdown
Set the Slow Shutdown feature to Enabled or Disabled.
30
Slow Sht Duration
If Slow Shutdown =
Enabled
, sets the time a boiler will
continue to run at the Stop Level after running above the Slow
Sht Threshold level, up to 9,999 seconds.
31
Slow Sht Threshold
Sets the Fire Rate above which a boiler will trigger the Slow
Shutdown feature.
32
O2 Warnings
Enables or disables AERtrim warning messages.
33
O2 Trim ID
Displays 4 digit AERtrim ID number. Pre-populated on all
Platinum units. Changes each time the unit is powered up.
34
Fixed ID
Displays the unit’s fixed 4 digit ID number. Pre-populated on all
Platinum units. Does not change.
35
O2 Trim Key
Displays the value of the AERtrim 4 digit license key. Pre-
populated on all Platinum units.
36
O2 Trim Menu
When set to Enabled, the AERtrim menu options appears.
37
BST Menu
When set to Enabled, the BST menu options appears.