BMK 750-3k Platinum Boiler OPERATION, SERVICE, and MAINTENANCE GUIDE
APPENDIX A: BOILER MENU DESCRIPTIONS
Page
90
of
178
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0116_0A
03/15/2017
Ph.: 800-526-0288
GF-201
TABLE A-3: CONFIGURATION MENU ITEM DESCRIPTIONS
See section 2-6 CONFIGURATION Menu for a range of choices and the default values.
The
Configuration
menu settings are Factory-Set in accordance with the requirements specified
with each individual order. No changes will be required under normal operating conditions.
TABLE A-3: CONFIGURATION MENU ITEM DESCRIPTIONS
MENU OPTIONS
DESCRIPTION
1
Internal Setpoint
Allows internal setpoint to be set from Lo Temp Limit of 40°F to
Hi Temp Limit of 240°F (4.4°C to 115.6°C).
2
Unit Type
Can be one of the following: BMK Blr Std, BMK Blr Std Dual,
BMK Blr LN, BMK Blr LN Dual.
3
Unit Size
Sets unit size, depending on the Unit Type:
750 MBH (220 kW), 1000 MBH (293 kW), 1500 MBH (439.6
kW), 2000 MBH (586.1 kW), 2500 MBH (732.6 kW), 3000 MBH
(879.2 kW)
4
Fuel Type
Allows selection of Natural Gas or Propane.
5
Boiler Mode
Only available if Unit Type = Boiler.
Allows selection of:
Constant Setpoint, Remote Setpoint, Direct Drive,
Combination, or Outdoor Reset Mode.
6
Remote Signal
Only available if Mode = Remote Setpoint, Direct Drive or
Combination. Used to set the type of external signal which will
be used when operating in the Remote Setpoint, Direct Drive
or Combination Mode.
7
Outdoor Sensor
Allows outdoor sensor function to be set to Enabled or
Disabled.
8
Bldg Ref Temp
Only available if Boiler Mode =
Outdoor Reset
. Allows the
building reference temperature to be set when operating a
boiler in the Outdoor Reset Mode.
9
Reset Ratio
Only available if Boiler Mode =
Outdoor Reset
. Permits setting
of Reset Ratio when operating boiler in the Outdoor Reset
Mode.
10
System Start Tmp
Only if Outdoor Sensor =
Enabled
. This menu item allows the
system start temperature to be set.
11
Setpt Lo Limit
Used to set the
minimum
allowable setpoint, from 40°F (4.4
°C)
up to the Setpt Hi Limit.
12
Setpt Hi Limit
Used to set the
maximum
allowable setpoint, from the Setpt Lo
Limit up to 210°F (98.9
°C)
.
13
Temp Hi Limit
This is the maximum allowable outlet temperature, up to 210°F
(98.9
°C)
. Any temperature above this setting will turn off the
unit. The temperature must then drop 5°F (2.75
°C)
below this
setting to allow the unit to run.
14
Max Valve Position
Sets the maximum allowable valve position for the unit.