BMK 750-3k Platinum Boiler OPERATION, SERVICE, and MAINTENANCE GUIDE
SECTION 5 – MAINTENANCE
Page
60
of
178
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0116_0A
03/15/2017
Ph.: 800-526-0288
GF-201
5.5 SAFETY DEVICE TESTING
Systematic and thorough tests of the operating and safety devices should be performed to
ensure that they are operating as designed. Certain code requirements, such as ASME CSD-1,
require that these tests be performed on a scheduled basis. Test schedules must conform to
local jurisdictions. The results of the tests should be recorded in a log book.
See The
Benchmark 750 – 3000 Installation and Startup Guide
, OMM-0115 (GF-200) for a
description and instructions for performing these tests.
5.6 BURNER INSPECTION
The burner assembly is located at the top of the unit's heat exchanger. The burner assembly
may be hot. Therefore, allow the unit to cool sufficiently before removing the burner assembly.
The following parts will be required for reassembly after burner inspection:
BMK 750/1000 Burner Inspection Parts
Part No.
Description
81143
Burner Gasket
81048
Flame Detector Gasket
81064
Blower Gasket
BMK 1500/2000 Burner Inspection Parts
Part No.
Description
81166
Burner Gasket (1 each)
88183
Burner Release Gasket (1 each)
81186
Burner Lower Release Gasket (1 each)
81048
Flame Detector Gasket (1 each)
BMK 2500/3000 Burner Inspection Parts
Part No.
Description
88173
Burner Upper Release Gasket
81180
Burner Gasket (Middle)
81185
Burner Lower Release Gasket
81048
Flame Detector Gasket (1 each)
NOTE:
Illustrations for the burner inspection procedure for all BMK Platinum models are presented first,
starting on the next page, followed by the written instructions.