AM Series Cascade Sequencer User Manual
Page
22
of
28
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0101_0D
04/29/2016
Ph.: 800-526-0288
GF-146-CS
2.2 Cascade Status Button
By pressing the Cascade Status button (Figure 2-1), the lower half of the display will change to
show the status of the cascade boilers (Figure 2-2). The designated number for each boiler in
the cascade system will be displayed, such as 1, 2, 3, 4, etc., up to 8. If there is a request for
heating for any heater, a flame icon will appear under that heater’s number. The absence of a
flame icon under the number represents a heater in standby mode. If there is a fault, a “wrench”
icon will be displayed under the heater’s number.
The Cascade Status display shown in Figure 2-2 indicates there are three heaters in the
cascade, with numbers 1 and 2 calling for heat, and number 3 in standby mode.
NOTE:
Due to the slow communication protocol, it may take up to 40 seconds for the Cascade
Status screen to update the status of an individual
boiler or water heater.
Figure 2-2: Cascade Status Display (When Cascade Button Pressed)
2.3 Submenu Navigation, and Parameter Settings
The sub-menu may be accessed, navigated, and parameters changed as instructed below.
Submenu Navigation and Parameter Settings
1. To access the Submenu, press and hold the
Home button
(Fig. 2-1) for eight seconds, then
release.
2. Use the
Up
or
Down
buttons
(Figure 2-1) to scroll through the list of Submenu parameters.
A dot to the left of the parameter indicates it is currently selected (Fig. 2-3).
Figure 2-3: Sub Menu - Selecting the Parameter to Change
3. When desired parameter is selected (dot), press
Ok button
. The dot will then appears to the
left of the parameter setting (Figure 2-4) and begins to blink, indicating it may be adjusted.
Figure 2-4: Sub Menu – Changing the Parameter Setting
A Flame Icon indicates
that this heater (#1) is
making a request for heat.
Numbers identify
each individual
heater in the
cascade system
No Flame Icon Indicates
that this heater (#3) is in
Standby Mode.
Dot indicates
parameter is
selected
Blinking dot = parameter
may be adjusted using UP