AM Series Cascade Sequencer User Manual
Page
20
of
28
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0101_0D
04/29/2016
Ph.: 800-526-0288
GF-146-CS
1.10 Removing the Cascade Sequencer
To remove the cascade sequencer from the system and return all units to normal boiler
operation
as un-sequenced, individual units
, perform the following procedure:
Removing the Cascade Sequencer
1. Connect the Cascade Sequencer to the last dependent boiler per Section 1.6 and set
cascade logic address to 0.
2. One at a time, connect the Cascade Sequencer to each dependent boiler per Section 1.6
and set cascade address to 0 until all dependent heaters are set to 0.
3. Connect the Master boiler per Section 1.6 and set cascade address to 0.
4. Unwire the cascade sequencer from the system and remove all daisy chain wiring between
the heaters.