AERCO Control System (ACS)
APPENDIX H:
ACS Modbus Address Assignments
11/22/2017
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
Page 135 of 139
OMM-0081_0F
Phone: 800-526-0288
GF-131
TABLE H2: ACS Standard Holding Register Address Mapping
Modbus Data
Address
Decimal (Hex)
Menu Item
Units and Range
Default/
Comments
156 (0x009C)
VALVE WAIT STATE
0 = Off
1 = Current State
If Option 1 or 2,
Default = 0
157 (0x009D)
BOOST TEMP
Hdr Low Limit to Hdr High
Limit
Default = 140
158 (0x009E)
VALVE WAIT TIME
0 to 500 Sec
Default = 120
159 (0x009F)
RETURN TEMP BOOST
DISABLE
Off, -80° to +80°
Default = Off (64726)
160 (0x00A0)
MODBUS ON.OFF
0 to 2
0 = Front Panel Off
1 = On
2 = Modbus Off
Default = 0
161 (0x00A1)
BOILER CONTROL SELECT
0 to 2
0 = None
1 = C-more
2 = MLX (BCM)
Default = 0
162 (0x00A2)
BOOST MAX TIMER
0 (Off), 1 to 999 Min
Default = 0
163 (0x00A3)
Thru
65535 (0Xffff)
(Reserved For Future Expansion) Undefined