AERCO Control System (ACS)
CHAPTER 3
: Operation
Page 64 of 139
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
11/22/2017
GF-131
Phone: 800-526-0288
OMM-0081_0F
3.14.1 CONSTANT SETPT MODE (Default):
Constant Setpoint Mode Programming
Menu & Option
Action
SETUP MENU
ENTER PASSWORD
Enter 159
RS485 MENU
Enter this menu if there are more than 2 boilers (default), otherwise
go to step 3
NUMBER NETW BOILERS
This setting is preset to 2. If more than 2 Boilers (default), enter
number (03, 04, etc)
NETW BOILER 01
ADDRESS= 001
Address 001 and 002 are preset. Enter other Network Addresses if
required (003, 004, 005, etc.)
FIELD ADJUST MENU
If Setpt is other than 160°F (default), enter this menu; otherwise go
to step 4
INTERNAL SETPT
Enter Setpoint temperature
CONFIGURATION MENU
If
BLR START LEVEL=20% & BLR STOP LEVEL=16%,
skip this
menu.
BLR START LEVEL
Enter Boiler Start Level Percent (default = 20%). See Appendix I.
BLR STOP LEVEL
Enter Boiler Stop Level Percent (default = 16%). See Appendix I.