5
5.3 Installation
The unit must be installed in the following position.
It is important that the unit is vertical in order for the condensation drainage to work properly.
•
When choosing the location it should be kept in mind that the unit requires maintenance regularly and that the inspection doors
should be easily accessible.
• Leave free space for opening the removable panels and for removal of the main components (see 3.4).
•
The outdoor air grilles if possible be put in the northern or eastern side of the building and away from other exhaust outlets like
kitchen fan exhausts or laundry room outlets.
Fig. 5.a
517 mm
Fig. 5.b
Fig. 5.c
Fig. 5.d
Fig. 5.f
Fig. 5.e
SPIRIT LEVEL
H=min. 60mm
Fig. 5.g
Summary of Contents for QR350ABP
Page 23: ...23 NOTE ...