9
Table 6.c Sound level
Preliminary data.
dBA figures are average spherical free-field, for comparitive use only.
6.2 Before Starting the System
When the installation is finished, check that:
• Filters are mounted correctly
• The unit is installed in accordance with the instructions
• The unit is correctly wired
• Eventual outdoor and exhaust air dampers and silencers are installed and that the duct system is correctly connected to the unit
• All ducts are sufficiently insulated and installed according to local rules and regulations
• Outdoor air intake is positioned with sufficient distance to pollution sources (kitchen ventilator exhaust, central vacuum system
exhaust or similar)
• The unit is correctly set and commissioned.
100%
Lw dB - SOUND POWER OCTAVE BAND
Lp dB(A)
63
125
250
500
1 K
2 K
4 K
8K
Tot
@3m
Intake
83
65
70
73
62
58
53
47
84
51
Supply
81
65
65
66
57
51
42
33
81
45
Extract
80
63
66
68
60
54
45
34
78
47
Exhaust
78
65
70
71
62
59
53
45
80
50
Breakout
81
69
67
69
62
56
48
36
82
48
80%
Lw dB - SOUND POWER OCTAVE BAND
Lp dB(A)
63
125
250
500
1 K
2 K
4 K
8K
Tot
@3m
Intake
73
61
67
69
59
56
50
43
75
47
Supply
72
61
63
65
56
50
41
31
74
43
Extract
73
60
63
65
57
51
42
31
74
44
Exhaust
73
61
66
67
58
55
49
41
75
46
Breakout
71
64
62
67
59
53
45
33
74
45
60%
Lw dB - SOUND POWER OCTAVE BAND
Lp dB(A)
63
125
250
500
1 K
2 K
4 K
8K
Tot
@3m
Intake
65
61
68
67
58
56
49
41
72
46
Supply
63
59
63
64
55
49
40
29
69
42
Extract
64
59
63
63
56
51
41
30
69
42
Exhaust
64
60
66
67
57
54
48
41
71
45
Breakout
59
64
63
65
57
51
43
31
70
44
40%
Lw dB - SOUND POWER OCTAVE BAND
Lp dB(A)
63
125
250
500
1 K
2 K
4 K
8K
Tot
@3m
Intake
55
55
67
55
49
47
40
31
68
39
Supply
53
53
62
52
47
41
32
22
63
35
Extract
58
52
60
51
47
42
32
22
63
34
Exhaust
55
54
66
55
49
47
40
31
67
39
Breakout
54
53
59
52
48
43
33
23
62
34
Summary of Contents for QR350ABP
Page 23: ...23 NOTE ...