background image

‘3’ – Blue. 
‘4’ – Yellow. 
‘5’ – Pink. 
‘6’ – Cyan. 
‘7’ – Purple. 
‘8’ – Orange.  

Parameter Number  Size (Byte) 

Available Settings 

Default value 

15 

0 ~ 8 

  

14)

 

Temperature Scale Setting  
Configure temperature sensor scale type, Temperature to report in Celsius or Fahrenheit. 
0 – Celsius (C). 
1 – Fahrenheit (F). 

Parameter Number  Size (Byte) 

Available Settings 

Default value 

20 

EU/AU  1 

0, 1 

US 

0, 1 

  

15)

 

Temperature Threshold Value to  Report  
Change threshold value for change in temperature to induce an automatic report for 

temperature sensor. Scale is identical setting in Parameter No.20. 

Setting of value 20 can be a change of -2.0 or +2.0 (C or F depending on Parameter No.20) 

to induce automatic report or setting a value of 2 will be a change of 0.2(C or F). 

Parameter Number  Size (Byte) 

Available Settings 

Default value 

21 

0~ 250 

20 

  

16)

 

Light intensity Threshold Value to Report  
Change threshold value for change in light sensor to induce an automatic report for 
temperature sensor. Scale: Lux. 

Parameter Number  Size (Byte) 

Available Settings 

Default value 

22 

0~ 10000 

100 

  

17)

 

Temperature Sensor Report  Interval  
This parameter is configured the time interval for temperature sensor report. This value is 

larger, the battery life is longer. And the temperature value changed is not obvious. 

Unit: Second. 

Parameter Number  Size (Byte) 

Available Settings 

Default value 

23 

1 - 32767 

3600 

  

18)

 

Light Sensor Report Interval  

This parameter is configured the time interval for light sensor report. This value is larger, the 

battery life is longer. And the light intensity changed is not obvious. 

Unit: Second. 

Parameter Number  Size (Byte) 

Available Settings 

Default value 

24 

1 - 32767 

3600 

Summary of Contents for ZWA005

Page 1: ...oth Tips on optimising the installation location of TriSensor can be found online in its digital guide 2 Remove the backplate from TriSensor 3 Insert one CR123A batteries with the correct orientation...

Page 2: ...blem with TriSensor visit http support aeotec com trisensor or contact our support team via aeotec com contact You can also learn more about TriSensor features configuration options and technical spec...

Page 3: ...sensitivity that motion detect 0 PIR sensor disabled 1 Lowest sensitivity 11 Highest sensitivity Parameter Number Size Byte Available Settings Default value 3 1 0 11 11 4 Binary Sensor Report Enable...

Page 4: ...m Value This parameter is configured the threshold value that alarm level for temperature When the current ambient temperature value is larger than this configuration value device will send a BASIC_SE...

Page 5: ...ight Sensor Report 0 Disable 1 Red 2 Green 3 Blue 4 Yellow 5 Pink 6 Cyan 7 Purple 8 Orange Parameter Number Size Byte Available Settings Default value 13 1 0 8 0 12 Led Color For Battery Report 0 Disa...

Page 6: ...or F Parameter Number Size Byte Available Settings Default value 21 2 0 250 20 16 Light intensity Threshold Value to Report Change threshold value for change in light sensor to induce an automatic rep...

Page 7: ...this parameter setting User should run the steps as blows for calibrating 1 Set this parameter value to default Assumes the sensor has been added in a Z Wave Network 2 Place a digital luxmeter close t...

Page 8: ...ON V1 The full text of the declaration is available from https support aeotec com trisensor doc Specifications Z Wave devices operate between 868 40 926 30 MHz depending on local restrictions It uses...

Reviews: