Transient Recording Configuration 

1.  With the instrument turned ON, press the 

 button to display the Waveform Capture 

screen. 

 

2.  Ensure 

 Transient is highlighted, then press  .  

 

If there are no transient detection sessions stored in the instrument, the Detection 

Schedule screen appears. 

 

If there are recordings in the instrument, the Detection List screen is displayed. In this 

case, press 

 to display the Detection Schedule screen. 

 

3.  Press the 

 function button under the 

 icon to display the Voltage Thresholds 

screen. At the top of the screen is the Threshold Set-up field. Options are: 

 

4V:

 The same voltage difference threshold applies to all phases and the neutral in the 

electrical hook-up 

 

3V+VN

: One threshold applies to the phases and one applies to neutral 

 

V1+V2+V3+V4

: Each phase and neutral has its own assigned threshold 

 

Depending on the electrical hook-up currently under measurement, not all these options 

may be available.  

 

4.  The setting in this field determines which of the four fields below it (1, 2, 3, and N) are 

editable: 

 

4V

: a single field is active for 1, 2, 3, and N. 

 

3V+VN

: one field is active for 1, 2, and 3; and another is active for N. 

 

V1+V2+V3+N

: each field is active. 

 

To edit a voltage threshold field, highlight it using the up and down arrow buttons, then 
confirm the selection by pressing  . Use the left and right arrows to select a digit, and the 

up and down arrows to change it. You can also use these buttons to select units (V or kV). 

Press   to confirm the edited field. 

5.  Press the A button to display the Current Thresholds screen. This is similar to the Voltage 

Threshold screen. You can select which thresholds apply to which phases, and specify the 

value of the threshold (1mA through 9999kA). As with the voltage thresholds, not all these 

options may apply to all electrical hook-up types. 

Note that current transients typically occur frequently. We recommend performing a current 

transient search only when looking for a specific type of transient. At other times, such as when 

you are primarily interested in voltage transients, you can effectively disable current transient 

searching by setting the threshold to its maximum value. 

 

 

 