background image

Crest Factor:

 

3 @ 200Arms with an error (due to CF) of 3% 

Working Voltage: 

600Vrms 

Common Mode Voltage: 

600Vrms 

Influence of Adjacent Conductor:

 

< 15mA/A at 50Hz 

Influence of DC on AC signal:

 

DC Current < 20A, < 5% 

Influence of Conductor Position in Jaw:

 

0.5% of mV output @ 50/60Hz 

Influence of Frequency:

 

40Hz to 1kHz: 3% of mV output 
1kHz to 10kHz: 12% of mV output 

Influence of Load:

 

< 3% of mA output from 40Hz to 1kHz 
< 12% of mA output from 1kHz to 10kHz 

Influence of Temperature:

 

 

Mechanical Shock:

 

Test per IEC 68-2-27 

Vibration:

 

Test per IEC 68-2-6 

 
Dimensions:

 

5.47 x 2.00 x 1.18" (139 x 51 x 30 mm) 

Weight: 

180 g (6.5 oz) 

 

Polycarbonate Material:

 

Jaws: Polycarbonate with 10% fiberglass charge, 

Red UL 94 V0 

Case: Polycarbonate 920A Gray 

Opening Operations - Life: 

> 50,000 

Output:

 

10 ft (3m) insulated lead with BNC connector 

 

 

 

SAFETY SPECIFICATIONS

 

≤ 

150 ppm/°K, or 0.15% of mV output per 10°K 

 

Influence of Humidity (10 - 90% RH):

 

≤ 

0.2% of mV output per 10°K @ 18°C to 28°C 

 

 

 

 

MECHANICAL SPECIFICATIONS

 

Operating Temperature:

 

14° to 131°F (-10° to +55°C) 

Storage Temperature:

 

-40° to 158°F (-40° to +70°C) 

Operating Relative Humidity:

 

50° to 95°F (10° to 35°C) 85% RH (without roll-off 
above 95°F [35°C]) 

Maximum Cable Diameter:

 

One Ø 0.78" (20mm), bus bar 0.78 x 0.2” (20 x 
5mm) 

Case Protection:

 

IP 40 (IEC 529) 

 

Drop Test:

 

Test per IEC 68-2-32: 1.0m drop on 38mm of  oak 
on concrete. 

 

 

 

Electrical: 

Double insulation or reinforced insulation between 
the primary or secondary and the outer case of the 
handle conforms to IEC 1010-2-32. 

Common Mode Voltage:

 

600V CAT III, Pollution Degree 2 

Dielectric Strength:

 

5550V, 50/60 Hz between primary, secondary 
and the outer case of the handle 

Electromagnetic Compatibility:

 

EN 50081-1 Class B 
EN 50082-2 Electrostatic discharge 

IEC 1000-4-2 

Radiated field IEC 1000-4-3 
Fast transients IEC 1000-4-4 
Magnetic field at 50/60 Hz IEC 1000-4-8 

 

 

 

ORDERING INFORMATION

 

AC Current Probe MN251T................ Cat #2132.59

 

www.

.com

[email protected]

1.800.561.8187

Reviews: