ELECTRICAL SPECIFICATIONS
Nominal Range:
200A
Measurement Range:
0.1 to 240A
Transformation Ratio:
Voltage output
Output Signal:
1mV/A
Accuracy and Phase Shift*:
Accuracy: 0.5 to 10A: 3.0% Reading ± 0.5mV
10 to 40A: 2.5% Reading ± 0.5mV
40 to 100A: 2.0% Reading ± 0.5mV
100 to 240A: 1.0% Reading ± 0.5mV
Phase Shift: 0.5 to 10A: Not Specified
10 to 40A: ≤ 5°
40 to 100A: ≤ 3°
100 to
240A: ≤ 2.5°
(*Reference conditions: 64 to 82°F (18 to 28°C), 20 to 75%
RH, external magnetic field < 40 A/m, 48 to 65Hz sine wave,
distortion factor less than 1%, no DC component, no external
current carrying conductor, test sample centered.)
Load impedance >
1MΩ.
Frequency Range:
40 to 10kHz
Limit Operating Conditions:
200A permanently to 1kHz
Derating above 3kHz: 200 A x (1/0.333 F), F in kHz