OMD94016 REV.
C
55
Alarm
A54 CAN ERROR
Description Internal error.
Possible
causes
•
Micro-controller communication problems.
Solutions
1) Contact our Technical Support Service.
Alarm
A55 PAR CABLE DISC
Description Parallel cable doesn't communicate.
Possible
causes
•
Parallel cable disconnected or damaged.
Solutions
1) Check the connection of cable
2) Contact our Technical Support Service.
Alarm
A56 MAINS UNBALANCE
Description The rectifier input voltage is unbalanced.
Possible
causes
•
Problems on the LV or MV distribution network
•
Defect of the measuring circuit.
Solutions
1) Check the input voltage
2) Contact our Technical Support Service.
Alarm
A63 START SEQ BLOCK
Description
During the UPS start-up a failure prevented the proper
execution of the sequence.
Possible
causes
•
Control devices in wrong position or operated improperly.
•
Possible internal fault.
Solutions
1) Make sure the position of the control devices (isolators,
selectors) is as specified in the procedures (see
“Installation and start-up” section).
2) If the alarm persists, contact our Technical Support
Service.