20
OMD94016 REV. C
LED 4
GREEN
Circuit breaker BCB closed and
battery charging
GREEN
Battery discharging or under TEST
ORANGE
Circuit breaker BCB open
RED
Battery fault (following a battery
test)
OFF
Battery not available
LED 5
GREEN
Inverter voltage within tolerance
and static switch closed
GREEN
Inverter overload or short-circuit
OFF
Inverter off or voltage out of
tolerance
LED 6
ORANGE
Re-transfer blocked
ORANGE
Static bypass switch closed
OFF
Static bypass switch open
LED 7
GREEN
Output circuit breaker OCB closed
OFF
Output circuit breaker OCB open
LED 8
ORANGE
Manual bypass switch MBCB
closed
OFF
Manual bypass switch MBCB open
LED 9
RED
Emergency power off (EPO)
activated
OFF
Normal operation