OMD94016 REV.
C
51
Alarm
A32 EPO BUS CLOSED
Description
The system is blocked due to the activation of the
emergency power off button.
Possible
causes
•
Activation of the (local or remote) emergency power off
button.
Solutions
1) Release the emergency power off button and reset the
alarm.
2) If the alarm persists, contact our Technical Support
Service.
Alarm
A33 ASYMMETRIC LOAD
Description
The positive and negative voltages measured on the DC
capacitors towards the middle point are different.
Possible
causes
•
Possible failure on the measuring circuit.
•
Possible fault of DC capacitors.
Solutions
1) Reset the system.
2) If the alarm persists, contact our Technical Support
Service.
Alarm
A34 SERVICE REQUIRED
Description A UPS check is necessary.
Possible
causes
•
Possible UPS fault.
Solutions
1) If the alarm persists, contact our Technical Support
Service.
Alarm
A35 DIESEL MODE
Description The UPS is supplied by the diesel generator.
Possible
causes
•
The auxiliary contact which activates the diesel generator
connected to the UPS is closed, and imposes this
operating mode.
Solutions
1) Wait for the diesel generator to stop as soon as the
mains voltage is restored.
2) Check the connection of the auxiliary contact which
signals the diesel generator start, to terminals XD1/XD2.
3) If the alarm persists, contact our Technical Support
Service.