84
Accuracy of control
Voltage ± 3%*
In the -15% to +10% range of the type voltage.
Current ±1.5%*
*always based on the end value
Limits
Voltage limit U
eff
Current limit I
eff
(for ...HRL1; ...HRLP1)
Power limit P (for ...HRLP1)
Peak current limit to Î=3xI
nom
at VAR mode
(for ...HRL1; ...HRLP1)
Relay outputs (only for ...H RL1 and ...H RLP1)
Changeover contact, contact material: AgSnO2 / Au plated
The relay can be used for low load circuits (> 5V 20mA), provided it
has not been preloaded with 230VAC.
Max. values: 250V, 6A, 180W, 1500VA
Insulation resistance 4kV / 8mm
Ambient temperature
35°C at ...F... (with forced cooling)
45°C with natural air cooling (without fan)
If the maximum ambient temperature is reduced, the maximum load
current can be increased up to 110% of the nominal current. The
following applies: 1% more current requires a temperature reduction
of 1°C.
The maximum ambient temperature can be increased up to a maxi-
mum of 55°C if the maximum load current is reduced. The following
applies: 1°C more ambient temperature requires a current reduction
of 2%. Use of the device in UL conditions up to a maximum ambient
temperature of 40°C.
Connection data, power connection
Grounding screw / nut for connecting the protective conductor to the
fixing adapter. Grounding also serves for EMC means (Y capacitor
4.7 nF).
Summary of Contents for THYRO-A
Page 28: ...28 Possible settings in THYRO TOOL FAMILY ...
Page 89: ...89 EN 10 Type overview Thyro A 1A 16 H 30 H Thyro A 1A 45 H 60 H ...
Page 90: ...90 75 190 Thyro A 1A 100 H Thyro A 1A 130 H 170 H M 10 for grounding ...
Page 92: ...92 Thyro A 1A 495A 650A Thyro A 1A 1000A 1500 A ...
Page 96: ...96 Thyro A 2A 495 650HF Thyro A 2A 1000 1500HF ...
Page 97: ...97 EN Dimension drawing Thyro A 3A with 16A 30A The dimension drawings are for type H RLP1 ...
Page 98: ...98 Dimension drawing Thyro A 3A with 45A 60A The dimension drawings are for type H RLP1 ...
Page 99: ...99 EN Dimension drawing Thyro A 3A with 100A The dimension drawings are for type H RLP1 ...
Page 100: ...100 Dimension drawing Thyro A 3A with 130A 170A The dimension drawings are for type H RLP1 ...
Page 101: ...101 EN Dimension drawing Thyro A 3A with 280A The dimension drawings are for type H RLP1 ...
Page 103: ...103 EN Thyro A 3A 1000 1500HF Thyro A 3A 495 650HF ...