This is done by altering the starting and finishing points of the control
characteristic curve. All common signals can be used.
As soon as the power controller reaches a limit value (U
max
, I
max
, P
max
),
this is indicated by LEDs (see page 29, LED messages).
The power controller has two setpoint inputs that are electrically isola-
ted from the mains and of which only one is ever active.
• setpoint 1: analog signal X2.4 (+); X2.3 (ground)
• setpoint 2: via system interface (bus module, THYRO-TOOL
FAMILY...)
The effective setpoint is the value when connected through. The set-
point input to be used is defined by configuring terminal X22.1 (see
page 36, Settings and operation).
3.3 Control modes
The power controller has various different control modes.
Before commissioning the power controller and selecting a control
mode, familiarization with the operating procedure and the effect
upon the application is important.
Control modes ...H1
Control mode
Control variable
U, U
2
highest conductor voltage
Control modes ...H RL1
Control mode
Control variable
U, U
2
highest conductor voltage
I, I
2
highest phase current
Control modes ...H RLP1
Control mode
Control variable
U, U
2
highest conductor voltage
I, I
2
highest phase current
P
total effective power
Fluctuations in mains voltage and changes in load are compensated
directly by bypassing the inert temperature control circuit. This me-
thod is therefore particularly fast (secondary control).
Summary of Contents for THYRO-A
Page 28: ...28 Possible settings in THYRO TOOL FAMILY ...
Page 89: ...89 EN 10 Type overview Thyro A 1A 16 H 30 H Thyro A 1A 45 H 60 H ...
Page 90: ...90 75 190 Thyro A 1A 100 H Thyro A 1A 130 H 170 H M 10 for grounding ...
Page 92: ...92 Thyro A 1A 495A 650A Thyro A 1A 1000A 1500 A ...
Page 96: ...96 Thyro A 2A 495 650HF Thyro A 2A 1000 1500HF ...
Page 97: ...97 EN Dimension drawing Thyro A 3A with 16A 30A The dimension drawings are for type H RLP1 ...
Page 98: ...98 Dimension drawing Thyro A 3A with 45A 60A The dimension drawings are for type H RLP1 ...
Page 99: ...99 EN Dimension drawing Thyro A 3A with 100A The dimension drawings are for type H RLP1 ...
Page 100: ...100 Dimension drawing Thyro A 3A with 130A 170A The dimension drawings are for type H RLP1 ...
Page 101: ...101 EN Dimension drawing Thyro A 3A with 280A The dimension drawings are for type H RLP1 ...
Page 103: ...103 EN Thyro A 3A 1000 1500HF Thyro A 3A 495 650HF ...