![AEG THYRO-A Operating Instructions Manual Download Page 32](http://html.mh-extra.com/html/aeg/thyro-a/thyro-a_operating-instructions-manual_8763032.webp)
32
3.9 Monitoring
Power controller and load circuit are monitored for malfunctions.
Messages are sent via LED (see page 29, LED messages), by bus or
by fault signalling relay K1 (see page 31, Fault signalling relay K1).
3.9.1 Monitoring the mains voltage
NOTE
Limit values for voltage monitoring
The following limit values apply for voltage monitoring:
- Undervoltage monitoring: -57% of type voltage
- Overvoltage monitoring: +10% of type voltage
This results in absolute limit values for the monitoring of the mains
voltage.
Tab. 3 Limit values for mains voltage monitoring
Only for ...H RL1 and ...H RLP1
In the event of more than 15% below the type voltage, the devices
can only be operated right up to the undervoltage limit if the electro-
nics are supplied from an external 24V source.
For ...H1, ...H RL1 and ...H RLP1
In default state, pulse inhibition is switched internally when the under-
voltage limit is exceeded, and fault signalling relay K1 de-energizes
(both can be set with THYRO-TOOL FAMILY).
Type
Undervoltage limit
Overvoltage limit
230V 99V
253V
400V
172V
440V
500V
215V
550V
600V
258V
660V
Summary of Contents for THYRO-A
Page 28: ...28 Possible settings in THYRO TOOL FAMILY ...
Page 89: ...89 EN 10 Type overview Thyro A 1A 16 H 30 H Thyro A 1A 45 H 60 H ...
Page 90: ...90 75 190 Thyro A 1A 100 H Thyro A 1A 130 H 170 H M 10 for grounding ...
Page 92: ...92 Thyro A 1A 495A 650A Thyro A 1A 1000A 1500 A ...
Page 96: ...96 Thyro A 2A 495 650HF Thyro A 2A 1000 1500HF ...
Page 97: ...97 EN Dimension drawing Thyro A 3A with 16A 30A The dimension drawings are for type H RLP1 ...
Page 98: ...98 Dimension drawing Thyro A 3A with 45A 60A The dimension drawings are for type H RLP1 ...
Page 99: ...99 EN Dimension drawing Thyro A 3A with 100A The dimension drawings are for type H RLP1 ...
Page 100: ...100 Dimension drawing Thyro A 3A with 130A 170A The dimension drawings are for type H RLP1 ...
Page 101: ...101 EN Dimension drawing Thyro A 3A with 280A The dimension drawings are for type H RLP1 ...
Page 103: ...103 EN Thyro A 3A 1000 1500HF Thyro A 3A 495 650HF ...