13
EN
Battery
Autonomy time
(for a battery charged 100% and at 25°C)
Linked
battery modules
Autonomy time (nominal load, pf = 0.9 lag.)
D.
1000
D.
1500
D.
2000
D.
3000
With integrated battery 6 min. 5.5 min. 6 min. 3.5 min.
1 extra battery module
31 min. 25 min. 33 min. 18 min.
2 extra battery modules 51 min. 46 min. 59 min. 34 min.
3 extra battery modules 82 min. 69 min. 88 min. 53 min.
4 extra battery modules 100 min. 90 min. 119 min. 69 min.
Rated direct voltage (intermediate circuit)
PROTECT D.
1000
36 V
PROTECT D.
1500
48 V
PROTECT D.
2000
72 V
PROTECT D.
3000
72 V
Float voltage
2.28 Vdc/cell (pre-set to 25°C)
charging voltage temperature dependent
Setting range
2.21 Vdc/cell – 2.31 Vdc/cell
in 0.01V increments
Batt.-charge power (max.) 1.4 Adc (PROTECT D.1000 / D.1500)
1.7 Adc (PROTECT D.2000 / D.3000)
Battery type
Valve regulated lead battery (VRLA)
Special type for high-current discharge
PROTECT D.
1000
3 blocks at 12V 9Ah
PROTECT D.
1000 BP
2 belts at 3 blocks at 12V 9Ah
PROTECT D.
1500
4 blocks at 12V 9Ah
PROTECT D.
1500 BP
2 belts at 4 blocks at 12V 9Ah
PROTECT D.
2000
6 blocks at 12V 9Ah
PROTECT D.
3000
6 blocks at 12V 9Ah
PROTECT D.
2030 BP
2 belts at 6 blocks at 12V 9Ah
Recharging times
~ 3h to 90% for internal battery
~9h
/
~15h
/
~21h
/
~27h with 1
/
2
/ 3 / 4 battery extension(s)