12
UPS output
Nominal output voltage
200/208/220/230/240 Vac ± 2%
Power reduction:
10% at 208V, 20% at 200V
Nominal frequency
50 Hz / 60 Hz ± 0.25 Hz
(Tolerance in battery mode
or free running in frequency
changer mode)
Synchronization range
50 Hz or 60 Hz ± 3 Hz
Synchronization speed
1 Hz / s
Power factor range
0.8 lag. to 0.9 cap.
for full power output
Power reduction:
10% to 0.5lag., 20% to 0.5
cap.
Voltage waveform
Sine, distortion
< 3% THD (linear load)
< 6% THD (non-linear load)
Crest factor
3:1
Overload behavior
to 110% continuously;
with mains supply
≥
110% – <130% for 5 min.
≥
130% – <150% for 15 s
≥
150% for 300 ms
Overload behavior
to 102% continuously;
with battery operation
≥
110% – <130% for 12 s
≥
130% – <150% for 2 s
≥
150% for 100 ms
Short-circuit behaviour
4.4 x I
N
for 100 ms