Description Adjustable parameters
Presetting
External battery
modules
Configures the amount of
external battery units
<0>
Battery charged
% to restart
[0%], [10%], [20%], ...[100%]
On battery operation the UPS output
is turned o as soon as the battery
capacity is below the selected level.
0 %
Automatic
battery tests
[enabled], [disabled]
enabled
Periodic
battery test
daily , weekly , monthly
weekly
The UPS on Battery notice and the Battery Low alarm do not activate
during a battery test.
For automatic battery tests to run:
The Automatic Battery Test setting must be enabled.
The UPS must be in Normal mode, with no active alarms.
The battery system being tested must have su icient reserve capacity.
Automatic battery tests run according to periodic battery test , unless disabled.
During the test, the UPS transfers to Battery mode and discharges the batteries
approximately 10 seconds under the existing load.
With reference to the input voltage, the Bypass voltage window must be within
the range of tolerances.