5-2
If the conditions mentioned above are satisfied, follow the steps below to start
up.
1. If there is an external battery cabinet, switch the circuit breaker of battery cabinet
to
ON
and confirm if manual bypass protection circuit breaker
Q3
is cut off and
switched to
OFF
.
2. Switch
on
Q2
and
Q4
.
The LCD monitor will start displaying. After initialization, the LCD screen will
show
”ON AUTO BYPASS”
. In the meantime, the UPS output is supplied by the
bypass source and the LED indicator of
”BYPASS”
will also light on.
3. Switch
Q1
to
ON.
If the input power source is within tolerance range, the UPS
power module will be ready to start up.
4. Press the “
I
” button for 3 seconds until you hear a “beep” and then release the
button. At this time, the inverter will start the synchronization with bypass source.
The UPS will automatically transfer from bypass mode to inverter mode, and the
output will be supplied by the inverter. The
”BYPASS”
LED indicator lights off
and the
”NORMAL”
LED indicator lights on.
5-2 Battery Startup Procedures (Single Unit)
1. Switch the circuit breaker of external battery cabinet to
ON
and confirm if
Q3
is
cut off and switched to
OFF
.
2. Press the “
I
” button for 3 seconds until you hear a “beep” and then release the
button.
3. The UPS will start up by DC-bus soft start. The inverter will be activated by
adopting the default frequency value.
4. When the inverter startup is completed, the UPS will transfer to Inverter mode
and the
”BATTERY”
LED indicator lights on.
5-3 Shutdown Procedures (Single Unit)
This operating procedure can cut off all the power supply. Be sure to confirm if the
loads are turned off first! Refer to following steps.
1. Press the “
O
” button for 3 seconds until you hear a “beep” and then release button.
The LCD screen will show
“SHUTDOWN UPS?”
, then selected
“YES”
and
press
“
”
to confirm.
If the UPS is originally in
- Normal mode: The UPS will transfer to bypass mode. The LCD screen will
show
”ON AUTO BYPASS”.
- Battery mode: The UPS will shut down the inverter and cut off the output power.
2. Switch off
Q1
.
3. Switch off
Q2
.
4. Confirm if the UPS is turned off and all the circuits are off.
5. If there is an external battery cabinet, switch off the circuit breaker of battery cabinet.
6. Switch off
Q4
.