8508 OPERATOR’S MANUAL – SECTION 3
10
Figure 3.5 – Location of AC Mains Barrier Strip
Full AC requirements by product model are de-
tailed below:
MODEL
208V (±10%)
400V (±10%)
8508
30A, 50/60 Hz
30A, 50/60 Hz
8512
30A, 50/60 Hz
30A, 50/60 Hz
8516
60A, 50/60 Hz
60A, 50/60 Hz
8520
60A, 50/60 Hz
60A, 50/60 Hz
near the bottom of the amplifier. Locate the
power block, which is mounted behind the fuse
and AC inlet panel (see
Figure 3.5
).
4.
Route the 10 AWG, 5 conductor power input
cable into the amplifier through the cable strain
relief (located on the fuse and AC inlet panel).
5.
Connect to the AC mains barrier strip as shown
in
Figure 3.6.
See
Appendix B
for wiring dia-
grams of the complete AC power systems.
6.
If connecting to an AC power cord, verify con-
nector wiring for phases, neutral and safety
ground. Verify that proper phase, neutral and
safety ground connections have been made at
the AC mains breaker.
The risk of lethal ELECTRICAL SHOCK
exists when connecting AC mains!
Disconnect the source before connect-
ing AC power wires to the amplifier’s AC
inputs.
DANGER
ELECTRIC SHOCK HAZARD. Power
supply wiring should only be performed
by a qualified, licensed electrician.
WARNING
Complete the following steps to connect the ampli-
fier to your three-phase power source:
1.
Wear safety goggles.
2.
Disconnect your AC power source.
3.
Open the access door on the back of the am-
plifier and locate the fuse and AC inlet panel