![Adveco EB0025 Product Manual Download Page 8](http://html1.mh-extra.com/html/adveco/eb0025/eb0025_product-manual_2858814008.webp)
EB0025
1. Technical Details
EB0025
415V/3ph/50Hz
10kA
16A/phase
Internal
400mm
300mm
160mm
5kg
Adveco Order Code:
Supply:
Fault level:
Max load current:
Aerial:
Height:
Width:
Depth:
Weight:
•
E0047: Control panel with gas to electric auto-changeover function. Includes main isolator feeding a
gas-fired water heater and an immersion heater, plus circuit breakers, volt-free contacts for BMS
support and heat recovery options.
•
E0012: GSM modem for automatic SMS or email notification of faults.
Included Parts:
•
EB0029: 9kW electric immersion heater assembly for use with BFC and SGS 30-60 water heaters
•
0304296S: 7.5kW electric immersion heater for use with SGE water heaters
Compatible Ancillaries:
•
SGE, SGS and BFC condensing gas-fired water heaters
•
HR001 Heat Recovery Box
Suitable for use with:
8
P R A C T I C A L , E F F I C I E N T & S U S T A I N A B L E B U I L D I N G S E R V I C E S S O L U T I O N S
EB0025-EB0028-EB0030 Control Panel -
Installation and maintenance manual