Destrat Pump
MB0001
To aid in thermal disinfection of the tank periodically, and to mix the contents
when operating on the backup element.
The bottom half of the tank is held at temperatures between 20°C and 40°C for
much of the operation of the system. The destrat pump is used to heat the entire
tank twice per week. It is also used when the standby immersion heater is
operating to create a mixing effect in the tank to overcome inaccuracies of flange
mounted stats.
Part Name:
Adveco Part Number:
Function:
Specifics
:
Testing:
1. With the power on, CB2 on, CB3 on, and CB5 on, and the BFC in fault for more than 5 minutes, confirm that
the pump is operating. If not, measure voltage between 4L2 and Earth. The correct reading is 230V. If 0V, test
KA1 and CB5. If 230V but pump does not run, check pump and replace if necessary. Once pump is confirmed
to operate, test Timeclock.
EB0030
3. Troubleshooting
Timeclock
TC1
E00TC1
To run the destrat pump twice a week for 2 hours.
Part Name:
Wiring Diagram Key:
Adveco Part Number:
Function:
Testing:
1. With the power on, confirm the timeclock is set to the correct day and time, that the timeclock is set to run
the program, and that the program includes two on periods per week, 3-4 days apart, for at least 2 hours but for
no more than 4 hours.
2. With the power on, put the timeclock into Hand (manual) operation and confirm the pump runs. If not, test
CB5 and pump, then replace timeclock.
3. With the power on, add a run period to the program for the day and time you are there and confirm that the
pump runs.
53
EB0025-EB0028-EB0030 Control Panel -
Installation and maintenance manual