23
Chapter 2
2.6.3 Isolated Outputs
Each of isolated output channels comes equipped with a Darlington tran-
sistor. All output channels share common emitters.
Please note that if an external voltage (5 ~ 40 VDC) is applied to an iso-
lated output channel while it is being used as an output channel, the cur-
rent will flow from the external voltage source to the UNO-3084. Please
take care that the current through each DO pin not exceed 200 mA. Figure
below shows how to connect an external output load to the UNO-3084 iso-
lated outputs. Please note that DO2 and DO3 may be configured as output
pins of Counter 0 and Counter 1.
Note:
UNO-3084 provides built-in examples to show how to
deliver digital output functionality. Refer to console
mode examples in C:\Program Files\Advan-
tech\UNO\UNO_IsaDIO\Examples\Console. (Please
install DI/O driver from the UNO CD to use these
examples)