SmartStart SL305
5.5
Mounting recommendations
•
It is possible to place the router on a flat surface,
•
mount the router on a wall using four holes in corners (Figure
) and screws with diam-
eter 4 mm,
•
attach the router on DIN rail EN 60715 with the included clip BB-SBD25.
The router meets EN 61439-1:2011 requirements/certifications for low-voltage switchgear
and control gear assemblies. These environments are described as:
•
A non-public, industry environment of low voltage with high interference,
•
a public environment of low voltage and without high interference.
For both of these environments, it is possible to mount the router to a switchboard, af-
ter which there is no need to have examination immunity or issues in connection with EMC
according to EN 61439-1:2011.
To comply with the EN 61439-1:2011 specification, follow these instructions:
•
For whip antennas it is recommended to observe a minimum distance of 6 cm from ca-
bles and metal surfaces on every side in order to avoid interference. When using an
external antenna separate from the switchboard it is necessary to fit a lightning conduc-
tor.
•
When mounting a router on sheet-steel we recommend using a cable antenna.
•
For all cables, we recommend to bind the bunch, and for this we recommend:
–
The length of the bunch (the combination of power supply and data cables) should
be a maximum 1.5 m. If the length of data cables exceeds 1.5 m or if the cable is
leading towards the switchboard, we recommend installing surge protectors.
–
Data cables must not have a reticular tension of
∼
230 V/50 Hz or
∼
120 V/60 Hz.
•
Sufficient space must be left between each connector for the handling of cables,
•
To ensure the correct functioning of the router we recommend the use of an earth-
bonding distribution frame for the grounding of the power supply of the router, data cables
and antenna within the switchboard.
13