8.4 CHILLER CAPACITY AND DERATE CHART
NOTES:
If operation of the chiller at less than 48°F is required, an inhibited propylene glycol
solution is required.
Do not operate the chiller below 20F fluid setpoint unless the unit has been specifically
configured for this duty.
Ambient conditions affect air cooled chiller operation and capacity. Standard rating
is at 95°F entering air temperature. For ambient air conditions greater than 95°F, chiller
derating will occur. For ambients over 95°F consult factory.
Standard chiller rating is at 50°F. For all other temperature settings, output tonnage is altered
as follows:
60
50
45
40
35
30
25
20
105%
100%
90%
80%
70%
60%
50%
40%
OUTPUT
TEMPERATURE
°F
FULL
AVAILABLE %
CAPACITY