BG-N4 Glycol Chiller
Page: 31
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: [email protected]
1.
The Setpoint range is from 20°F to 60°F.
2.
Once acknowledged, the unit will control to the new setpoint temperature. Press
the Back button repeatedly to return to the Setpoints screen or press the home
button to return to the Home screen.
C.
Hi Deviation. The High Deviation value programs the controller to sound the alarm if the
process temperature exceeds the set difference from setpoint. For example, Hi Deviation
= 10°F, Setpoint = 50°F. Hi deviation alarm will sound if the temperature reaches 60°F.
1.
The factory default is 10°. The range for the Hi Deviation is from 0°F - 50°F.
2.
Once acknowledged, press the Back button repeatedly to return to the Setpoints
screen or press the home button to return to the Home screen.
D.
Lo Deviation. The Lo Deviation value programs the controller to sound the alarm if the
process temperature exceeds the set difference from setpoint. For example, Lo Deviation
= 10°F, Setpoint = 50°F. Lo deviation alarm will sound if the temperature cools to 40°F.
1.
The factory default is 10°. The range for the Lo Deviation is from 0°F - 50°F.
2.
Once acknowledged, press the Back button repeatedly to return to the Setpoints
screen or press the home button to return to the Home screen.
D.
Low Flow (optional feature not included on all units). The Low Flow value programs
the controller to sound an alarm if the process flow goes below the low flow set value.
For example, if the flow set value is 3 GPM and if the flow goes below 3 GPM an alarm
condition is indicated. Note: the low flow alarm feature is only available with the purchase
of the optional flow meter.
1.
The factory default is 0 GPM. The range for the Low Flow is from 0 to 100 GPM.
2.
Once acknowledged, press the Back button repeatedly to return to the Setpoints
screen or press the home button to return to the Home screen.
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Hi Deviation
Cancel
Adjust
OK
Setpoints
Process Setpoint
Hi Deviation
Lo Deviation
Low Flow
Back
Pick
Go
10°F
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Change Setting
Hi Deviation
Success
Acknowledge
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Lo Deviation
Cancel
Adjust
OK
Setpoints
Process Setpoint
Hi Deviation
Lo Deviation
Low Flow
Back
Pick
Go
10°F
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Change Setting
Lo Deviation
Success
Acknowledge
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Low Flow
Cancel
Adjust
OK
Setpoints
Process Setpoint
Hi Deviation
Lo Deviation
Low Flow
Back
Pick
Go
3 GPM
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Change Setting
Low Flow
Success
Acknowledge
Summary of Contents for BG-N4 Series
Page 2: ......
Page 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Page 12: ...Page 12 THIS PAGE INTENTIONALLY BLANK ...
Page 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Page 40: ...Page 40 THIS PAGE INTENTIONALLY BLANK ...
Page 46: ...Page 46 THIS PAGE INTENTIONALLY BLANK ...
Page 54: ...Page 54 THIS PAGE INTENTIONALLY BLANK ...
Page 75: ...END 2021 ADVANTAGE ENGINEERING INC RE 20210218 ...
Page 76: ......