22
MegaTron Quick Steps
After second update is complete, power down and
remove USB. Power back on (after 20 seconds) and
go to the Configure menu.
>HOME SETUP<
SETPOINTS
DATE/TIME
CALIBRATION
CONFIGURE
TIMERS
HISTORY
CUSTOMIZE
WATER METER
ALARMS
RELAYS
From here push
SYS INFO
(Button 9) and confirm
that the unit now has the new version and that the
CARD version is also current (consult factory for
current).
>CONFIGURE<
PASSWORD
CONTRAST
RELAYS
TEMP SCALE
NETWORK
HISTORY
SYS INFO
FLOW SW
FACTORY
SYSTEM INFORMATION:
XS MEGATRON CONTROLLER
ADVANTAGE CONTROLS INC.
FRMWARE REV: KA.10.03A Jan 29 2018
S/N: SERIAL#
CARD VER: 5
Warning:
If the card revision has not updated
to the newer version, the sensor function will not
work correctly. A few power cycles may be needed
to get the system card updated. The mA input
and communications card (if present) may need
to be removed with the power off and a power
cycle performed. Once the system card version is
updated, power back down and reinstall the mA and
communications cards.
Cloning User Settings for other XS Units
The XS has the ability to copy the User Settings
from one XS to another. This process is referred to
as cloning.
3
4
5
2
1
8
9
0
7
6
SET UP
RUN
CANCEL
HELP
BACK
ENTER
HOME
3
4
5
2
1
8
9
0
7
6
SET UP
RUN
CANCEL
HELP
BACK
ENTER
HOME
3
4
5
2
1
8
9
0
7
6
SET UP
RUN
CANCEL
HELP
BACK
ENTER
HOME
Step 1:
With the controller powered up, plug the USB drive
into the XS USB port. The USB DRIVE DETECTED
pop-up window will appear. Select
→ Config → USB
(Config to USB) by using the Arrow buttons. Then
press ENTER.
XS Controller
3 ALARMS!
RELAYS
Friday, February 6, 2015 15:50:47 Wk1
SYS1: Towers 1-4
COND: 0 uS/cm
pH: 3.2
ORP: 548 mV
TEMP1: 68°F
WM1: 0.0
WM2: 0.0
FLOW: ON
DR
USB DRIVE DETECTED
--> Config --> USB
PRESS UP/DOWN KEYS TO CHANGE
PRESS ENTER TO ACCEPT
The User settings will be saved to the USB drive under
the file name “CONFIG.BIN”. The pop-up window will
close when the copy is completed.
Step 2:
Plug the USB drive into the XS that you would like
to copy the User Settings to. The USB DRIVE
DETECTED pop-up window will appear.
Select
→ USB → Config
(USB to Config) by using
the Arrow buttons. Then press ENTER.
CAUTION:
Do not choose → Config →
USB again or you will save over your USB
contained CONFIG.BIN file.
XS Controller
3 ALARMS!
RELAYS
Friday, February 6, 2015 15:50:47 Wk1
SYS1: Towers 1-4
COND: 0 uS/cm
pH: 3.2
ORP: 548 mV
TEMP1: 68°F
WM1: 0.0
WM2: 0.0
FLOW: ON
DR
USB DRIVE DETECTED
--> USB --> Config
PRESS UP/DOWN KEYS TO CHANGE
PRESS ENTER TO ACCEPT
The User Data will be loaded into the XS from the
USB drive. Once the pop-up window closes, cloning
has been completed.
Notes:
• Not all customized names will be cloned.
• If you have trouble reading clone files, insure
that the XS you are cloning has current
firmware.
XS Controller - USB Functions
!
!