Table 11. Parameter list (Continued)
API
#
Read /
Write
Address
Parameter Name
Type
Parameter Description
Dec
Hex
138
Read
4386
1122
#3 Status PC r
UINT32
Power controller #3: Status PC - read
Bit 0: Output (pulses) on
Bit 1: Power controller OK)
Bit 2: Mains OK
Bit 3: Remote setpoint
Bit 6: Pulse lock (with ack.)
Bit 7: Pulse lock (auto-ack.)
Bit 8: Regulator lock
Bit 12: Left rotation field
Bit 13: Output restricted
Bit 14: Max output reached
Bit 16: Active limit
Bit 17: U limit
Bit 18: I limit
Bit 19: I
peak
limit
Bit 20: P limit
Bit 21: Temperature limit
Bit 22: Limit external feedback signal
Bit 24: RAMP starting mode
Bit 25: MOSI starting mode
Bit 26: MOSI starting mode I
RMS
Bit 27: MOSI starting mode I
peak
Advanced Energy
®
Thyro-PX
™
Anybus
®
Modbus TCP
57010166-00A
Thyro-PX
™
Anybus
®
Modbus TCP
25