Table 11. Parameter list (Continued)
API
#
Read /
Write
Address
Parameter Name
Type
Parameter Description
Dec
Hex
97
Read
4304
10D0
#1 L3 External control r FLOAT
Power controller #1: L3 External control
- read
98
4306
10D2
99
Read
4308
10D4
#2 Analog setpoint r
FLOAT
Power controller #2: Analog setpoint -
read
100
Read
4310
10D6
#2 Motor pot. setpoint r
FLOAT
Power controller #2: Motor
potentiometer setpoint - read
101
Write
4312
10D8
#2 Fieldbus setpoint w
FLOAT
Power controller #2: Fieldbus setpoint -
write
102
Read
4314
10DA
#2 Actual setpoint r
FLOAT
Power controller #2: Actual setpoint -
read
103
Write
4316
10DC
#2 Error setpoint w
FLOAT
Power controller #2: Error setpoint -
write
104
Read
4318
10DE
#2 Total power r
FLOAT
Power controller #2: Total power - read
105
Read
4320
10E0
#2 Alpha r
FLOAT
Power controller #2: Alpha - read
106
Read
4322
10E2
#2 TimeOn r
FLOAT
Power controller #2: Time on - read
107
Read
4324
10E4
#2 Output r
FLOAT
Power controller #2: Output - read
108
Read
4326
10E6
#2 Frequency r
FLOAT
Power controller #2: Frequency - read
109
Read
4328
10E8
#2 Energy counter r
FLOAT
Power controller #2: Energy counter -
read
110
Read
4330
10EA
#2 Error PC r
UINT32
Power controller #2: Error PC - read
Bit 4: Synchronization error
Bit 5: Phase missing
Bit 6: Fuse broken
Bit 7: Thyristor short circuit
Bit 16: Internal communication error
Bit 17: U clipping
Bit 18: I clipping
Bit 19: Negative power
Bit 20: Temperature probe error
Bit 21: Overtemperature
Bit 24: I/O error
Advanced Energy
®
Thyro-PX
™
Anybus
®
Modbus TCP
57010166-00A
Thyro-PX
™
Anybus
®
Modbus TCP
21