2500 Series  

Fire Smoke Dampers 

Date 

Issue 

Spec. No. 

Page No. 

04/03/14  Rev 2  CE –FSD Sub 

PATENT APPLIED FOR 

HEVAC Floor Installation -  E120 

Pre Installation Notes  

 

1.  Ensure that the damper is kept in a 

clean dry environment and that there 
is no damage to the damper. 

2.  Remove all packaging and transit ties 

before installation. 

Installation Procedure  

 
1. The opening in the floor slab must be cleaned, free of dust and any other contaminants which could impair the mortar 

adhesion. A clearance gap 25mm (min) to 50mm (max) must be maintained around the expansion frame of the fire damper 
(barrier contractor). 

2. The tabs on the factory fitted galvanized steel expansion frame will be bent out to tie the damper into the floor with the 

penetration seal. 

3.  The damper should be fitted flush to the top edge of the opening. 
4. The underside of the damper should be shuttered up with 25mm rigid rock wool firebatt Min Density 140kg/m3 cut to 

interference fit and supported from below, this must be left in situ.  

5. The “Penetration Seal” must have a structural and fire rated compatibility with both the barrier and the damper and have 

sufficient strength to retain the fire damper within the floor slab in a fire situation. (4:1 Mortar Mix). 

6. Pour the Mortar Mix into the gap between damper and floor slab to half way and ensure all the small gaps are filled, leaving 

no air pockets. Then pour the top layer up to the installation frame face smoothing off if necessary. 

7. The ductwork connecting to the dampers long spigot must overlap by 40mm. The ductwork connecting to the short spigot 

must overlap the spigot by 40mm, leaving 10mm clearance for any duct expansion in a fire situation.  

8. All ductwork connections must be sealed with an approved ductwork sealer, and fixed with low resistance fixings such as: 

aluminium alloy rivets or nylon bolts. 

9.  All connecting ductwork must be independently supported within 1meter of the connections. 

Maintenance Procedure 

 



These dampers are installed as a life-safe product and will require regular physical and visual examinations. It is essential 

that that the assembly is kept in a clean, dust free condition at all times. 



It is essential that an access door has been provided in the adjacent ductwork to facilitate the inspection and maintenance. 



Ensure that no physical restriction of the blades has occurred during the installation process. 



Remove any dirt or debris built up in the damper, apply a little WD lubricant or light oil, any excessive oils should be wiped 

away. 



Check the operation of any ancillary products that may be fitted. 



Examine the fusible link to ensure that no corrosion has occurred and that the plates are free from distortion and are in good 

condition to operate when required. 



Close the blade pack by manual operation and  examine the blades to ensure; 



They are in the fully closed position and have located in the ramps. 



They are all position in the frame correctly i.e. square to the frame. 



They are all in a clean condition. 



The period between maintenance checks can best be ascertained by system conditions or as directed by local regulations for 

ventilation plant and ancillaries, but should not exceed a maximum interval in excess of twelve months. 



The report should be completed following the Maintenance Procedure  included within this document. 

Installation & Maintenance Instructions 

Summary of Contents for 2500 Series

Page 1: ...ble link that prevent the damper from opening if the temperature has reached 720 C With the introduction of Construction Product Regulation on the 1st July 2013 all fire dampers are required to meet t...

Page 2: ...ght to change any information without prior notice Burrell Way Thetford Norfolk IP24 3QU England Tel 44 0 1842 753624 Fax 44 0 1842 762032 Email sales advancedair co uk 2500 Series Fire Smoke Dampers...

Page 3: ...Cambered grade 430 stainless steel Top Bottom Jambs Profiled grade 430 stainless steel riveted to damper frame Minimum Duct Size Rectangular 100mm x 100mm case size 250mm x 250mm Circular 100mm diamet...

Page 4: ...i o s TBC AFS Blockwork Wall BS EN 1366 2 120 min E120 ve i o s AFS Adjustable Frame System PATENT PENDING With the tighter requirements of the CPR and Building regulations with regard to CE labellin...

Page 5: ...ngland Tel 44 0 1842 753624 Fax 44 0 1842 762032 Email sales advancedair co uk 2500 Series Fire Smoke Dampers Date Issue Spec No Page No 04 03 14 Rev 2 CE FSD Sub PATENT APPLIED FOR 5 Sizing Informati...

Page 6: ...using 750mm wide units tests performed in a clean system at suitable pressures and are P re ssu r e D r o p s F u l l y O p e n 1 1 0 1 0 0 1 0 0 0 1 1 0 1 0 0 V e lo c it y m s Pressure drop Pa 6 1 0...

Page 7: ...s aluminium alloy rivets or nylon bolts 9 All connecting ductwork must be independently supported within 1meter of the connections 10 An Access cover should be fitted on the appropriate side of the ba...

Page 8: ...y 7 The ductwork connecting to the dampers long spigot must overlap by 40mm The ductwork connecting to the short spigot must overlap the spigot by 40mm leaving 10mm clearance for any duct expansion in...

Page 9: ...tilation plant and ancillaries but should not exceed a maximum interval in excess of twelve months The report should be completed following the Maintenance Procedure included within this document Pre...

Page 10: ...ce checks can best be ascertained by system conditions or as directed by local regulations for ventilation plant and ancillaries but should not exceed a maximum interval in excess of twelve months The...

Page 11: ...ion of Fire Dampers must be done by competent trained persons who are familiar with the type of product They should follow the following essential safety practices Wear appropriate PPE gloves footwear...

Page 12: ...ght to change any information without prior notice Burrell Way Thetford Norfolk IP24 3QU England Tel 44 0 1842 753624 Fax 44 0 1842 762032 Email sales advancedair co uk 2500 Series Fire Smoke Dampers...

Page 13: ...tch wiring for damage where applicable Check damper for cleanliness and clean where necessary Check the condition of the blades and seals rectify and report where necessary Confirm the safety closure...

Reviews: