2500 Series  

Fire Smoke Dampers 

Date 

Issue 

Spec. No. 

Page No. 

04/03/14  Rev 2  CE –FSD Sub 

PATENT APPLIED FOR 

HEVAC Wall Installation - E120 

Installation & Maintenance Instructions 

Installation Procedure  

 

1.  Vertical builders work barrier to have an appropriately 

sized lintel to ensure an opening clearance for the 
expansion frame. 

2.  The opening in the wall must be cleaned, free of dust and 

any other contaminants which could impair the mortar 
adhesion. A clearance gap 25mm (min) to 50mm (max) 
must be maintained around the expansion frame of the 
fire damper (barrier contractor). 

3.  The damper shall be fitted centrally in the wall opening. 
4.  The tabs on the factory fitted galvanized steel expansion 

frame shall be bent out to tie the damper into the wall with 
the penetration seal. 

5.  The “Penetration Seal” must have a structural and fire 

rated compatibility with both the barrier and the damper 
and have sufficient strength to retain the fire damper 
within the wall in a fire situation. (4:1 Mortar Mix). 

6.  The Mortar Mix will be applied up to the installation frame 

face, take care not to leave any air pockets in the mix. 

7.  The ductwork connecting to the damper spigots must 

overlap by 40mm, leaving a 10mm clearance for any duct 
expansion in a fire situation.  

8.  All ductwork connections must be sealed with an 

approved ductwork sealer, and fixed with low resistance 
fixings such as: aluminium alloy rivets or nylon bolts. 

9.  All connecting ductwork must be independently supported 

within 1meter of the connections. 

10. 

An Access cover should be fitted on the appropriate side 

of the barrier to enable inspections and maintenance 
work.

 

Pre Installation Notes 

 

1.  Ensure   that   the   damper   is   kept   in   a   clean   dry 

environment and that there is no damage to the damper. 

2.  Remove all packaging and transit ties before installation. 

Maintenance Procedure 

 



These dampers are installed as a life-safe product and will require regular physical and visual examinations. It is essential 

that that the assembly is kept in a clean, dust free condition at all times. 



It is essential that an access door has been provided in the adjacent ductwork to facilitate the inspection and maintenance. 



Ensure that no physical restriction of the blades has occurred during the installation process. 



Remove any dirt or debris built up in the damper, apply a little WD lubricant or light oil, any excessive oils should be wiped 

away. 



Check the operation of any ancillary products that may be fitted. 



Examine the fusible link to ensure that no corrosion has occurred and that the plates are free from distortion and are in good 

condition to operate when required. 



Close the blade pack by manual operation and  examine the blades to ensure; 



They are in the fully closed position and have located in the ramps. 



They are all position in the frame correctly i.e. square to the frame. 



They are all in a clean condition. 



The period between maintenance checks can best be ascertained by system conditions or as directed by local regulations 

for ventilation plant and ancillaries, but should not exceed a maximum interval in excess of twelve months. 



The report should be completed following the Maintenance Procedure  included within this document. 

Summary of Contents for 2500 Series

Page 1: ...ble link that prevent the damper from opening if the temperature has reached 720 C With the introduction of Construction Product Regulation on the 1st July 2013 all fire dampers are required to meet t...

Page 2: ...ght to change any information without prior notice Burrell Way Thetford Norfolk IP24 3QU England Tel 44 0 1842 753624 Fax 44 0 1842 762032 Email sales advancedair co uk 2500 Series Fire Smoke Dampers...

Page 3: ...Cambered grade 430 stainless steel Top Bottom Jambs Profiled grade 430 stainless steel riveted to damper frame Minimum Duct Size Rectangular 100mm x 100mm case size 250mm x 250mm Circular 100mm diamet...

Page 4: ...i o s TBC AFS Blockwork Wall BS EN 1366 2 120 min E120 ve i o s AFS Adjustable Frame System PATENT PENDING With the tighter requirements of the CPR and Building regulations with regard to CE labellin...

Page 5: ...ngland Tel 44 0 1842 753624 Fax 44 0 1842 762032 Email sales advancedair co uk 2500 Series Fire Smoke Dampers Date Issue Spec No Page No 04 03 14 Rev 2 CE FSD Sub PATENT APPLIED FOR 5 Sizing Informati...

Page 6: ...using 750mm wide units tests performed in a clean system at suitable pressures and are P re ssu r e D r o p s F u l l y O p e n 1 1 0 1 0 0 1 0 0 0 1 1 0 1 0 0 V e lo c it y m s Pressure drop Pa 6 1 0...

Page 7: ...s aluminium alloy rivets or nylon bolts 9 All connecting ductwork must be independently supported within 1meter of the connections 10 An Access cover should be fitted on the appropriate side of the ba...

Page 8: ...y 7 The ductwork connecting to the dampers long spigot must overlap by 40mm The ductwork connecting to the short spigot must overlap the spigot by 40mm leaving 10mm clearance for any duct expansion in...

Page 9: ...tilation plant and ancillaries but should not exceed a maximum interval in excess of twelve months The report should be completed following the Maintenance Procedure included within this document Pre...

Page 10: ...ce checks can best be ascertained by system conditions or as directed by local regulations for ventilation plant and ancillaries but should not exceed a maximum interval in excess of twelve months The...

Page 11: ...ion of Fire Dampers must be done by competent trained persons who are familiar with the type of product They should follow the following essential safety practices Wear appropriate PPE gloves footwear...

Page 12: ...ght to change any information without prior notice Burrell Way Thetford Norfolk IP24 3QU England Tel 44 0 1842 753624 Fax 44 0 1842 762032 Email sales advancedair co uk 2500 Series Fire Smoke Dampers...

Page 13: ...tch wiring for damage where applicable Check damper for cleanliness and clean where necessary Check the condition of the blades and seals rectify and report where necessary Confirm the safety closure...