CS2 SERIES
–OPERATION MANUAL(EN)-A-2017-11-16
40 / 41
4: High Hold
(High Energized Hold)
5: DO
(Digital Output);
ry#hy
0038h
0000~5000
Hysteresis of Relay3
0
R/W
ry#rd
0039h
0000~5999
(0.1second)
Energized Delay Time of Relay3
0
R/W
ry#fd
003Ah
0000~5999
(0.1second)
De-Energized Delay Time of Relay3
0
R/W
ry$md
003Bh
0~5
Relay4 Energized Mode
0: oFF
(no use);
1: Lo
(Low Energized);
2: Hi
(High Energized)
3: Lo Hold
(Low Energized Hold)
4: High Hold
(High Energized Hold)
5: DO
(Digital Output);
6: Go-1.2
(Go function compare with SP1 & SP2);
7: Go-2.3
(Go function compare with SP2 & SP3);
0
R/W
ry$hy
003Ch
0000~5000
Hysteresis of Relay4
0
R/W
ry$rd
003Dh
0000~5999
(0.1second)
Energized Delay Time of Relay4
0
R/W
ry$fd
003Eh
0000~5999
(0.1second)
De-Energized Delay Time of Relay4
0
R/W
rYrst
003Fh
Reset for Relay Energized Hold
0:
No
1:
Yes
0
R/W
bank
0040h
The addres is for CS2-VA
、
CS2-RS &
CS2-PR
Bank selection
bit0
=1; Bank1 selected
bit1
=1; Bank2 selected
bit2
=1; Bank3 selected
bit0=bit1=bit2=0
; Bank0 selected
0
R/W
【
ECI Group
】
Name
Address
Range
Explain
Initial
Write/Read Note
ecI1
0041h
0~5
External Control Input 1
0: nonE
(None);
1: rEL.PV
(Relative PV);
2: PV.HLd
(PV Hold);
3: M.rSt
(Reset for Maximum & Minimum);
4: rY.rSt
(Reset for Relay Hold);
5: di
(Digital Input);
1
R/W
ecI2
0042h
0~5
External Control Input 1
0: nonE
(None);
1: rEL.PV
(Relative PV);
2: PV.HLd
(PV Hold);
3: M.rSt
(Reset for Maximum & Minimum);
4: rY.rSt
(Reset for Relay Hold);
5: di
(Digital Input);
2
R/W
ecI3
0043h
0~5
External Control Input 1
0:
nonE (None);
1:
rEL.PV(Relative PV);
2:
PV.HLd(PV Hold);
3:
M.rSt(Reset for Maximum & Minimum);
4:
rY.rSt(Reset for Relay Hold);
5:
di(Digital Input);
3
R/W
debnc
0044h
5~255
ECI debouncing
5~255 *8mSec
12
R/W
【
AO Group
】
Name
Address
Range
Explain
Initial
Write/Read Note
aOtyp
0045h
0~5
Analog Output Type
4
R/W