Adjust the machinery structure to the higher signal output status(or any
higher status).
F
−
3
caLhi
6478h
699b
h
caLhi
(CAL.Hi): Field Calibration High
.
The high calibration is not need the
exactly "span" to calibrate because of the
"field calibration" function could be
calibrating any higher point.
Waiting for the value till stable,
pressed
Key to read signal high
of sensing device.
Waiting for above reading stable
(around 3~5seconds), press
Key again to complete the
calibration higher point, and go to
[
caLhs
].
F
−
4
caLhs
250)0
250)
0
2
50)0
caLhs
(CAL.HS): the value to be set is
relative to Field Calibration high point.
Settable range: -19999~29999
Shift
Up
Down
Enter
F
−
5
Csel
deflt
deflt
field
Csel
(C.SEL): Calibration parameter
selection;
As the user finished the procedures of
field calibration, the field calibration datum
has been saved in EEProm and it can't
change the default(factory) calibration
datum . Even the field calibration has been
done, the user can still select either default
calibration or field calibration.
Programmable:
deflt
(default):
factory calibration
points and factors
field
(field):
field calibration points
and factors
Up
Down
Enter
◘
If the user select field
calibration of the
[
lOsc
]
(step
A-4) and
[
hIsc
]
(A-5) will be
replaced by
the
[
caLls
]
and
[
caLhs
]
which it
can not to be
change by anyone. If user has to
change the scaling, it's the only
way to access field calibration
level to set in
[
caLls
]
(step F-2)
and
[
caLhs
]
(step F-4).
◘
Please double check the
[
lOsc
]
(step A-4) and
[
hIsc
]
(A-5)
whether
are correct after
selection the
deflt
or
field.
Go back to Measuring Page