CS2 SERIES
–OPERATION MANUAL(EN)-A-2017-11-16
23 / 41
■
Relay Group
(The group will not be displayed except the relay function is to be specified )
INDEX
FUNCTION DESCRIPTION
PARAMETERS & SETTING SET
relay
group
RELAY GROUP INDEX PAGE
In following pages, press
for
1 second to return the RELAY
GROUP INDEX PAGE.
B
−
1
rYsb
)0
00)
0
9
9(9
rYsb
(rY.Sb): Start band of Relay energized
Start Delay
Fig.2
Start Delay Time
Start Band
Hi Setting
Relay
Energized
ON
Inhibit
Inhibit
[
rYsb
]
[
ry_.sp
]
[
rYsd
]
Settable range: 0~9999 digits
Shift
Up
Down
Enter
B
−
2
rYsd
)0)0
)0)
0
(
5(9
rYsd
(rY.Sd): start delay time for Relay
energized
Settable range:
0:00.0~9(M):59.9(S)
Shift
Up
Down
Enter
B
−
3
ry!md
hi
hi
hIhld
ry!md
(rY1.Md): Relay 1 energized mode
Hi / Lo / Go Relay Energized
hi
lo
Go-12
[
ry_.sp
]
[
ry_.sp
]
[
ry_.md
]
Hi Setting
Hi Relay Energized
ON
Lo Setting
Lo Relay Energized
ON
ON
Go Relay Energized
ON
ON
Relay Energized Latch & Reset
Hi. HLd(Hi Latch)
Relay Energized
ON
Reset Relay Latch
by ECI or Front Key
ON
Level Trigger
Hi Setting
hIhld
[
ry_.md
]
rYrst
[
eci._
]
[
ry_.sp
]
Programmable:
off
(Off):
Turn off the Relay and
indication LED.
lo
(Lo):
Low Level Energized;
Relay will energize when PV <
Set-Point.
hi
(Hi):
High Level Energized;
Relay will energize when PV >
Set-Point.
hIhld
(Hi.HLd)/
lOhld
(Lo.HLd):
High / Low Level energize and
latch; As the PV Higher (or
lower) than set-point, the relay
will be energized to latch
except manual reset by from
key in
[
User Level
],
front key
function or terminals of
E.C.I.
closed
do
(DO):
Digital Output;
Relay is energized by RS485
command directly, but no
longer to compare with
set-point of relay.
Up
Down
Enter
B
−
4
ry!hy
)0
00)
0
5
0)0
ry!hy
(rY1.HY): Relay 1 Hysteresis
Energized / De-energized
Delay & Hysteresis
Fig.3
ON
Hysteresis
De
-e
n
e
rg
iz
e
d
d
e
la
y
ti
m
e
Hi Setting
Relay
Energized
[
ry_.sp
]
[
ry_.hy
]
[
ry_.rd
]
[
ry_.fd
]
E
n
e
rg
ize
d
d
e
la
y
ti
m
e
Settable range: 0~5000 digits
Shift
Up
Down
Enter
B
−
5
ry!rd
)0)0
)0)
0
(
5(9
ry!rd
(rY1.rd): Relay 1 energized delay
time
Settable range:
0:00.0~9(M):59.9(S)
Shift
Up
Down
Enter
NEXT PAGE