CS2 SERIES
–OPERATION MANUAL(EN)-A-2017-11-16
36 / 41
Name
Address
Range
Explain
Initial
Write/Read Note
ry@rd
0024h
0000~5999
(0.1second)
Energized Delay Time of Relay2
0
R/W
ry@fd
0025h
0000~5999
(0.1second)
De-Energized Delay Time of Relay2
0
R/W
ry#md
0026h
0~5
Relay3 Energized Mode
0: oFF
(no use);
1: Lo
(Low Energized)
2: Hi
(High Energized)
3: Lo Hold
(Low Energized Hold)
4: High Hold
(High Energized Hold)
5: DO
(Digital Output);
1
R/W
ry#hy
0027h
0000~5000
Hysteresis of Relay3
0
R/W
ry#rd
0028h
0000~5999
(0.1second)
Energized Delay Time of Relay3
0
R/W
ry#fd
0029h
0000~5999
(0.1second)
De-Energized Delay Time of Relay3
0
R/W
ry$md
002Ah
0~5
Relay4 Energized Mode
0: oFF
(no use);
1: Lo
(Low Energized);
2: Hi
(High Energized)
3: Lo Hold
(Low Energized Hold)
4: High Hold
(High Energized Hold)
5: DO
(Digital Output);
6: Go-1.2
(Go function compare with SP1 & SP2);
7: Go-2.3
(Go function compare with SP2 & SP3);
1
R/W
ry$hy
002Bh
0000~5000
Hysteresis of Relay4
0
R/W
ry$rd
002Ch
0000~5999
(0.1second)
Energized Delay Time of Relay4
0
R/W
ry$fd
002Dh
0000~5999
(0.1second)
De-Energized Delay Time of Relay4
0
R/W
rYrst
002Eh
Reset for Relay Energized Hold
0:
No
1:
Yes
0
R/W
RESERVED
002Fh
No use unless CS2-VA & CS2-RS
bank
The addres is for CS2-VA & CS2-RS
bit1
=1; Bank2 selected
bit2
=1; Bank3 selected
bit0
=bit1-bit2=0; Bank0 selected
0
R/W
[
ECI Group
]
Name
Address
Range
Explain
Initial
Write/Read Note
ecI1
0030h
0~5
External Control Input 1
0:nonE
(None);
1:rEL.PV
(Relative PV);
2:PV.HLd
(PV Hold);
3: M.rSt
(Reset for Maximum & Minimum);
4:rY.rSt
(Reset for Relay Hold);
5:di
(Digital Input);
1
R/W
ecI2
0031h
0~5
External Control Input 1
0:nonE
(None);
1:rEL.PV
(Relative PV);
2:PV.HLd
(PV Hold);
3: M.rSt
(Reset for Maximum & Minimum);
4:rY.rSt
(Reset for Relay Hold);
5:di
(Digital Input);
2
R/W