RK3000 High Frequency Power Supply
Operating Manual
Page 38 of 73
Press ENTER and the ‘Max Set Size” Parameter Screen will appear.
Note: The values for the max TR ratings can be found on the TR nameplate. Use values
for the output of the diode bridge and not the AC transformer (if both are shown).
The acceptable range for the rated TR maximum primary current is presented to the right
to the word “Range.” In this example the acceptable range is 1 to 500 amperes.
The present TR rated maximum primary current value is presented to the right of the word
“Enter.” In this example, the rated maximum primary current is 160 amps.
If the rated TR primary current is to be changed, simply press the numeric keys that
correspond to the new value (the old value will be overwritten) and press ENTER. If the
present rated TR primary current value is acceptable, simply press ENTER without
making any changes. In either case, the second display “Max Sec Current” will appear.
The acceptable range for the rated TR maximum secondary current is presented to the
right of the word
“Range.” In this example the range is from 1 to 3000 milliamps.
The present rated TR maximum secondary current value is displayed to the right of the
word “Enter.” In this example the rated maximum secondary current is 1000 milliamps.
If the present rated TR maximum secondary current is to be changed, simply press the
numeric keys corresponding to the new value (the old value will be overwritten) and press
ENTER. If the present rated TR maximum secondary current value is acceptable, simply
press ENTER, w
ithout making any changes. In either case, the third display “Max Sec
Voltage” will appear.
The acceptable range for the rated TR maximum average secondary voltage is presented
to the right to the word “Range.” In this example the acceptable range is 1 to 99 kilovolts.
The present rated TR maximum average secondary voltage value is presented to the
right of the word “Enter.” In this example the rated TR maximum average secondary
voltage is 45 kilovolts.
If the present rated maximum secondary current is to be changed, simply press the
numeric keys corresponding to the new value (the old value will be overwritten) and press
ENTER. If the present rated maximum secondary current value is acceptable, simply
press ENTER without making any changes
Press the DOWN or UP keys to view more prompt screens or press ESC to return the
display to either the Electrical Reading Screen or the Device Status Screen depending on
the screen you were in prior to pressing the PROMPT key.
RED-01
Max Primary Current
Range: 1-500 Amperes
Enter: 160
RED-01
Max Sec Current
Range: 1-3000 mA
Enter: 1000
RED-01
Max Sec Voltage
Range: 1-99 kV
Enter: 45