Communication loss
time
CD72
Setting Range 0.1 ~ 100.0SEC
Default Value
0.5SEC
Set communication loss time. When communication loss time over
CD72 setting, Inverter will active as CD76 selected.
Note : This function does not effect in standby condition.
Communication
error counter
CD73
Setting Range
0 ~ 10
Default Value
3
When communication error continuous time more than CD73 setting.
Inverter will active as CD76 selected.
Address setting
CD74
Each drive must have unique identified addrss if they are controlled by
RS485 communication. Each address connot be duplicated.
0 : broadcast to all inverter.
Setting Range
1 ~ 255
Default Value
1
Transmission speed
CD75
Setting the transmission speed between computer and drive.
0 : 2400 bits/second.
1 : 4800 bits/second.
2 : 9600 bits/second.
3 : 19200 bits/second.
Setting Range
0 ~ 3
Default Value
0