Abstract

The Advanced Discovery System (ADICOS

®

) is used for early detection of fires in industrial 

environments. It is comprised of various, separate detector units. By parameterizing and 

arranging the detectors appropriately, the system fulfills a predefined detection goal. The ADI-

COS system ensures reliable early detection of embers and smoldering fires even in adverse 

environments.

ADICOS GSME fire gas detectors detect at an early stage gases that are characteristic for 

developing fires. They detect both open and concealed smoldering fires. Highly sensitive and 

at the same time robust, they are ideal for fire gas detection in industrial environments – and 

already in the incipient stage. With the ADICOS software, all detector states and concentration 

curves can be displayed graphically. Sensitivities as well as alarm thresholds can be param

-

eterized individually for each detector. The GSME fire gas detectors can be used in almost any 

indoor plant area, taking into account the air flow conditions.

Four  parameterizable  semiconductor  gas  sensors  monitor  and  evaluate  the  concentration 

curve of these gases according to multi-criteria technology. This enables the GSME detectors 

to distinguish real fires from interference signals. In industrial environments, this often occurs 

under harsh conditions, e.g. due to vehicle exhaust fumes, dust, mist or vapor.

ADICOS GME-X20 detectors are designed for operation in hazardous dust atmospheres up to 

ATEX zone 20.

Summary of Contents for GSME-X20

Page 1: ...dustrieelektronik GmbH Helmholtzstr 21 38 40 41747 Viersen Germany 49 2162 3703 0 info gte de GSME X20 Supplementary Instruction Manual for GSME X20 Fire Gas Detector IP64 DO NOT OPEN IN GAS LOADED AT...

Page 2: ...oltzstr 21 38 40 41747 Viersen GERMANY Support hotline 49 2162 3703 0 E Mail support adicos gte de 2023 GTE Industrieelektronik GmbH This document and all figures contained may not be copied changed o...

Page 3: ...for fire gas detection in industrial environments and already in the incipient stage With the ADICOS software all detector states and concentration curves can be displayed graphically Sensitivities as...

Page 4: ...6 2 3 Personnel Qualification 7 2 4 Handling Electrical Voltage 7 2 5 Modifications 7 2 6 Accessories and Spare Parts 7 3 Structure 8 3 1 Overview 8 3 2 Cable assignment 8 3 3 Display elements 9 4 In...

Page 5: ...notes are used through this manual DANGER This combination of symbol and signal word indicates an immediately dangerous situation that will lead to death or severe injuries if not avoided WARNING This...

Page 6: ...l Data must be met Any deviating use requires prior consultation with the manufacturer Compliance with this manual as well as all applicable country specific provisions is also part of the intended us...

Page 7: ...ectors requires an electrical voltage that can trigger an explosion in potentially explosive atmospheres Do not open enclosure De energize the entire detector system and secure against unintentionally...

Page 8: ...gland 3 2 Cable assignment Wire Color Signal Signal limit contact 1 black Operating voltage 21 6 40 V DC non polarized 1 white 2 black Relay output X6 e Alarm NO1 2 white Relay output X6 a Alarm NO1 3...

Page 9: ...lack NO 6 white C 3 3 Display elements Signal Dome The signal dome is a translucent element It includes the status LED to indicate the operating condition of the X20 detectors The light signals of the...

Page 10: ...explosion due to electrical voltage in hazardous areas The electronics of ADICOS GSME X20 works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres Do not ope...

Page 11: ...x protected connection boxes with respective approval Do not bend connection cable Observe minimum bending radius Chap 9 Technical Data 5 Commissioning DANGER Risk of explosion due to electrical volta...

Page 12: ...plosion in potentially explosive atmospheres Do not open enclosure De energize the entire detector system and secure against unintentionally reactivation for all wiring work Replace the closed detecto...

Page 13: ...power consumption with heating VA 14 M Bus voltage signal V mA max 40 V non polarized max 30 mA Thermal physical data Ambient Temperature C 20 50 C Relative humidity 95 non condensing Sensor data Sens...

Page 14: ...able YR Year of production variable ART Nr Article number variable TEMP Ambient temperature IP Degree of protection COM Nr Communication number variabel VDC VA Voltage range maximum pow er consumption...

Page 15: ...15 ADICOS GSME X20 408 2410 004 EN22 Appendix 10 Appendix 10 1 ADICOS Mounting Plate A A 1 5 0 1 5 0 1 3 0 1 3 0 6 4 A A...