The construction of the base includes 5 pillars and a base to support the heater, leaving cut out for the
fan to drop into. The bench cut out is 560mm x 230mm from the rear of the base.
The assembly includes a 30mm air gap behind the rear sheet to combustible material. Use Skamotec
off cuts to space out from the wall. The side walls continue to the rear wall, enclosing the gap.
The minimum Ventilation area must be included below the base of the heater and below the cap ( 9
and 10). The ventilation can be included in the front to the dimensions at L or on the sides, shown as
Q. The same total vent area is included below the base of the firebox, and at the top below the ceiling
cap height of the chimney chase, in either case.
STEP 1.
STEP 2.