Industrial
Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO:
www.adfweb.com
Phone +39.0438.30.91.31
User Manual
PROFIBUS Master / Modbus TCP Slave - Converter
Document code: MN67579_ENG Revision 2.002 Page 19 of 32
By pressing the “
Manual Module
” button from the “PROFIBUS Device” window (Fig. 6) the “Add Module Manually” window appears (Fig. 8).
In this window is possible to add a Module manually, i.e. writing the configuration of the module (in hexadecimal).
The means of the fields are:
In the field “
Description of Module
” a name of the Module is defined;
In the field “
Insert the Configuration of Module (HEX)
” the configuration of the module is defined. The configuration must be
write in hexadecimal mode (without prefix “0x” o “$”).
To modify a Module inserted manually, is neccessary to do a double click on the module to change in the “Select Module” list (Fig. 7, point
(1)). It is possible to change only the module inserted manually.
Note:
The Values inserted in the table must between 00 and FF
Figure 8: “Add/Modify Module Manually” window