DALI MAP:
Internally to the converter, there are two different arrays of bytes. The data inside them are different:
DALI memory array in IN: data read from DALI network;
DALI memory array in OUT: data written to DALI network.
Structure of the DALI memory array in OUT (DALI
SNMP)
For each DALI node configured, the converter will reserve 8 bytes: using the SW67850, it is possible to map the required bytes into the
SNMP objects.
Below, it is possible to see the generic structure of 8 bytes reserved for each DALI node:
Offset
Description
0
Status
of DALI node
1
ADV
of DALI node
2
Response received after command
from DALI node
3
Bit 0, 1, 2, 3 (least significant) =
Type
of DALI node
Bit 4, 5, 6, 7 (most significant) =
Version
of DALI node
4
Min. settable value
of DALI node