 ADFweb.com Srl – IT31010 – Mareno – Treviso                                                      INFO:  

www.adfweb.com

      Phone +39.0438.30.91.31            

 

User Manual   

DALI / SNMP Agent

 

 

Document code: MN67850_ENG     Revision 1.000   Pagina 9 di 42

 

 

 

LEDS: 

 
The device has got five LEDs that are used to give information of the functioning status. 
The various meanings of the LEDs are described in the table below. 

 

LED 

Normal Mode 

Boot Mode 

1: Device State (green) 

Blinks slowly (~1Hz) 

Blinks quickly:

 Boot state 

Blinks very slowly (~0.5Hz):

 update in progress 

2: DALI communication 
(yellow) 

Blinks when DALI communication is running 

Blinks quickly:

 Boot state 

Blinks very slowly (~0.5Hz):

 update in progress 

3: SNMP communication 
(yellow) 

Blinks when SNMP communication is running 

Blinks quickly:

 Boot state 

Blinks very slowly (~0.5Hz):

 update in progress 

4: Comm. error (yellow) 

Turns ON when DALI devices defined are not present 

Blinks quickly:

 Boot state 

Blinks very slowly (~0.5Hz):

 update in progress 

5: Ethernet Link (green) 

ON:

 Ethernet cable connected 

OFF:

 Ethernet cable disconnected 

ON:

 Ethernet cable connected 

OFF:

 Ethernet cable disconnected 

 

Summary of Contents for HD67850-B2-N

Page 1: ...m Product HD67831 Serial www adfweb com Product HD67832 BACnet IP Master www adfweb com Product HD67833 BACnet IP Slave www adfweb com Product HD67834 CAN www adfweb com Product HD67835 CANopen www ad...

Page 2: ...40 DISCLAIMER 41 OTHER REGULATIONS AND STANDARDS 41 WARRANTIES AND TECHNICAL SUPPORT 42 RETURN POLICY 42 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you...

Page 3: ...etc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembl...

Page 4: ...al Electronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual DALI SNMP Agent Document code MN67850_ENG Revision 1 000 Pagina 4 di 42 EXAMPLE OF CO...

Page 5: ...es ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual DALI SNMP Agent Document code MN67850_ENG Revision 1 000 Pagina 5 di 42 CONNECTION SCHEME Figure 1 Conne...

Page 6: ...y SNMP Additional isolation Power Supply DALI for HD67850 B2 N version Mountable on 35mm Rail DIN Wide power supply input range 8 24V AC or 12 35V DC Wide temperature range 40 C 85 C 40 F 185 F CONFIG...

Page 7: ...SNMP Agent Document code MN67850_ENG Revision 1 000 Pagina 7 di 42 POWER SUPPLY The devices can be powered at 8 24V AC and 12 35V DC For more details see the two tables below VAC VDC Vmin Vmax Vmin Vm...

Page 8: ...wo functions mode depending of the position of the Dip1 of Dip Switch A The first with Dip1 of Dip Switch A at OFF position is used for the normal working of the device The second with Dip1 of Dip Swi...

Page 9: ...quickly Boot state Blinks very slowly 0 5Hz update in progress 2 DALI communication yellow Blinks when DALI communication is running Blinks quickly Boot state Blinks very slowly 0 5Hz update in progr...

Page 10: ...the lighting system from a simple light switch to lighting management systems for entire office complexes with thousands of light sources Using ADFweb com s DALI converters any light source including...

Page 11: ...k for programming the converter and for SNMP communication The Ethernet connection must be made using Connector2 of HD67850 B2 with at least a Category 5E cable The maximum length of the cable should...

Page 12: ...e the available software that runs with Windows called SW67850 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last versi...

Page 13: ...contains the entire device s configuration A device s configuration can also be imported or exported To clone the configurations of a Programmable DALI SNMP Agent Converter in order to configure anoth...

Page 14: ...is the possibility to change the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connec...

Page 15: ...ne 39 0438 30 91 31 User Manual DALI SNMP Agent Document code MN67850_ENG Revision 1 000 Pagina 15 di 42 In the section Software Settings it is possible to enable disable some keyboard s commands for...

Page 16: ...dress that you want to give to the SNMP side is defined In the field SUBNET Mask the SubNet Mask of the SNMP side is defined In the field GATEWAY the default gateway that you want to use is defined Th...

Page 17: ...NG Revision 1 000 Pagina 17 di 42 DALI ACCESS By pressing the DALI Access button from the main window for SW67850 Fig 2 the window Select the DALI Device Present in the Network appears Fig 4 This sect...

Page 18: ...D is sent as Trap when the data from DALI side change If the field On CMD is checked the OID is sent as Trap when the a DALI command is received If the field On Timer is checked the OID is sent as Tra...

Page 19: ...its Bytes the dimension of the OID is defined For Int type the dimension is in bit for String type the dimension is in bytes In the field Description the description name of the OID is defined In the...

Page 20: ...nect the Ethernet cable Insert the IP 192 168 2 205 Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn OFF the Devi...

Page 21: ...ting Try with another PC Try to restart the PC Check the LAN settings Check the Wi Fi settings If you are using the program inside a Virtual Machine try to use in the main Operating System If you are...

Page 22: ...test the communication it is possible to use the available software that runs with Windows called DALI Console It is downloadable on the site www adfweb com and its operation is described in this docu...

Page 23: ...ructured in this way Menu bar Fig 9 Point 1 it is possible to open the setup window and see the informations about the DALI Console software Network view Fig 9 Point 2 it is possible to see all the DA...

Page 24: ...net communication with the converter fixed to 10000 In the field CONSOLE PORT insert the communication port used for the Ethernet communication with the converter defined with SW67850 In the fields SC...

Page 25: ...ed to the converter It is possible to reprogram the entire DALI network deleting and reprogramming the ID to all DALI devices Full Search or set the ID only to the DALI devices without it Partial Sear...

Page 26: ...d test the functioning of the network DEVICES The means of the fields for DEVICE INFO are In the field Device Type the type of DALI device is printed In the field Software version the software version...

Page 27: ...ADV value In the GROUP MEMBERSHIP section it is possible to see the Groups which the selected DALI device is in The checked checkboxes mean that the device is in the correspondent groups the unchecke...

Page 28: ...DALI group For set commands it is possible to insert the value to set in the field xx As soon as the command to send is selected the command is sent in order to send the same command more times it is...

Page 29: ...Manual DALI SNMP Agent Document code MN67850_ENG Revision 1 000 Pagina 29 di 42 SCENES By selecting a DALI scene from the Network view it is possible to see the devices that have programmed the select...

Page 30: ...commands it is possible to insert the value to set in the field xx As soon as the command to send is selected the command is sent in order to send the same command more times it is possible to press t...

Page 31: ...array in OUT data written to DALI network Structure of the DALI memory array in OUT DALI SNMP For each DALI node configured the converter will reserve 8 bytes using the SW67850 it is possible to map t...

Page 32: ...value of DALI node 6 Each bit has a different meaning 0 means Group not configured 1 means Group configured Bit 0 less significant Group 0 Bit 1 Group 1 Bit 2 Group 2 Bit 3 Group 3 Bit 4 Group 4 Bit...

Page 33: ...e 1 2 ADV to set on DALI node 2 3 ADV to set on DALI node 3 4 ADV to set on DALI node 4 5 ADV to set on DALI node 5 6 ADV to set on DALI node 6 7 ADV to set on DALI node 7 8 ADV to set on DALI node 8...

Page 34: ...t on DALI node 26 27 ADV to set on DALI node 27 28 ADV to set on DALI node 28 29 ADV to set on DALI node 29 30 ADV to set on DALI node 30 31 ADV to set on DALI node 31 32 ADV to set on DALI node 32 33...

Page 35: ...47 48 ADV to set on DALI node 48 49 ADV to set on DALI node 49 50 ADV to set on DALI node 50 51 ADV to set on DALI node 51 52 ADV to set on DALI node 52 53 ADV to set on DALI node 53 54 ADV to set on...

Page 36: ...y byte Description 64 ADV to set on Group 0 65 ADV to set on Group 1 66 ADV to set on Group 2 67 ADV to set on Group 3 68 ADV to set on Group 4 69 ADV to set on Group 5 70 ADV to set on Group 6 71 ADV...

Page 37: ...P Agent Document code MN67850_ENG Revision 1 000 Pagina 37 di 42 ADV SETTING BROADCAST Memory byte Description 80 ADV to set Note The range of ADV can be from 0 to 255 The minimum and the maximum valu...

Page 38: ...e increased of 1 every times that the command must be sent on DALI 129 ID of DALI device to command for commands most significant bit must be set to 1 as DALI specifications 0 63 Single DALI device 64...

Page 39: ...com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual DALI SNMP Agent Document code MN67850_ENG Revision 1 000 Pagina 39 di 42 MECHANICAL DIMENSIONS Figure 16 Mechanica...

Page 40: ...converter feeds the DALI bus N not present the converter doesn t feed the DALI bus Connectors Type 2 Fixed 5mm Screw Terminal Enclosure Type B 2M 35mm DIN Rail mounting Device Family HD67850 DALI SNM...

Page 41: ...untries with separate collection systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable...

Page 42: ...exchange or repair it please do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about th...

Reviews: