User Manual
Modbus / CAN - Datalogger
Document code: MN67324_ENG Revision 1.200 Page 20 of 44
UPDATE DEVICE:
By pressing the “
Update Device
” button it is possible to load
the created Configuration into the device; and also the
Firmware, if is necessary.
If the Ethernet version is used, in order to load the parameters
or update the firmware in the device, follow these instructions:
Turn OFF the Device;
Put Dip1 of ‘Dip-Switch A’ in ON position;
Turn ON the device
Connect the Ethernet cable;
Insert the IP “
192.168.2.205
”;
Select which operations you want to do;
Press the “U
pdate Device
” button to start the upload;
When all the operations are “OK” turn OFF the Device;
Put Dip1 of ‘Dip-Switch A’ at OFF position;
Turn ON the device.
If you know the actual IP address of the device, you have to use this procedure:
Turn ON the Device with the Ethernet cable inserted;
Insert the actual IP of the Converter;
Select which operations you want to do;
Press the “
Execute update firmware
” button to start the upload;
When all the operations are “OK” the device automatically goes at Normal Mode.
Figure 6a: “Update Device” window (Ethernet version)